| 2017-02-13 08:24:38 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | | | | COMMENTS: | | | | | | 1. PLEASE ADDRESS BUILDING AND ZONING COMMENTS. | | | 2. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO | | | INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC | | | 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE | | | VERBIAGE IN CODE. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|