| 2018-05-13 09:29:08 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | BANYAN CAY FOUR STORY HOTEL **FOUNDATION ONLY** |
| | ***THRESHOLD BUILDING***, POST TENSION 6"-8" SLABS, FRT |
| | TRUSSES, TYPE IIA |
| | ARCHITECT - ADACHE GROUP ARCHITECTS, DANIEL E. ADACHE |
| | AR7073 |
| | ENGINEER - MUE ENGINEERS, INC (29348), MARCUS O. |
| | UNTERWEGER, PE63860 |
| | MEP - TLC ENGINEERING |
| | MECHANICAL - JORGE E. REYES, PE54904 |
| | ELECTRICAL - RALPH BAEZA, PE42641 |
| | PLUMBING - JORGE E. REYES, PE54904 |
| | |
| | 1. SEE THRESHOLD REVIEW. A 100% COMPLETE SI AGREEMENT |
| | WILL BE ACCEPTED VIA EMAIL; THREE ORIGINALS REQUIRED |
| | AFTER PRELIMINARY REVIEW. |
| | |
| | 2. SEE IMPACT REVIEW. IF YOU WOULD LIKE TO SUBMIT A |
| | REQUEST TO HAVE IMPACT FEES COLLECTED PRIOR TO ISSUANCE |
| | OF VERTICAL CONSTRUCTION, SEND THE REQUEST (ADDRESSED |
| | TO ROBERT BROWN, BUILDING OFFICIAL) VIA EMAIL TO |
| | [email protected]. THE BUILDING OFFICIAL IS REQUIRED TO |
| | MAKE THIS REQUEST OF PALM BEACH COUNTY AND IT IS NOT |
| | GUARANTEED TO BE GRANTED. |
| | |
| | 3. FROM PREVIOUS REVIEWS, SEOR IS TO REVIEW THE SOILS |
| | REPORT. RESPONSE LETTER STATES THAT STRUCTURAL DRAWINGS |
| | HAVE BEEN REVISED TO REFERENCE THE REPORT FROM |
| | UNIVERSAL. SEE SHEET S0.00, 310000-FOUNDATIONS, REVISE |
| | TO INCORPORATE GEOTECHNICAL REPORT (CURRENTLY "XXXX"), |
| | OR ADVISE WHERE THIS REVISION HAS BEEN MADE (PAGE |
| | NUMBER). |
| | |
| | 4. SEE SIGNATURE REVIEW. |
| | |
| | 5. DISTANCE TO PROPERTY LINES - OK; PLEASE ADVISE, WHEN |
| | WILL REPLAT BE FINALIZED? |
| | |
| | 10. FS471, FS481, ARCHITECTS AND ENGINEERS HAVE |
| | REQUIREMENTS TO HAVE A TITLE BLOCK ON EACH SHEET WHICH |
| | INCLUDES THE PRINTED NAME AND LICENSE NUMBER, COMPANY |
| | LICENSE NUMBER (AS WELL AS OTHER INFORMATION). |
| | |
| | STRUCTURAL ENGINEER OF RECORD HAS A COMPLIANT TITLE |
| | BLOCK ON ALL S SHEETS. |
| | MEP AND ARCH TITLE BLOCKS NEED BUSINESS LICENSE NUMBER |
| | ADDED. PLEASE REVISE BUT ONLY UPLOAD PAGES WHICH CHANGE |
| | DUE TO CODE RELATED COMMENTS TO AVOID ANOTHER 100% |
| | REVIEW BY ALL TRADES (BUT FIX TITLE BLOCK SO REVIEW |
| | DOES NOT FAIL WHEN REVISIONS ARE SUBMITTED). |
| | |
| | 11. SEE VERTICAL BUILDING PERMIT, COMMENTS #2 AND #3 |
| | REGARDING EXIT DISCHARGE AND ACCESSIBLE MEANS OF |
| | EGRESS. ARCHITECT MAY PROVIDE A SIGNED AND SEALED |
| | LETTER INDICATING UNDERSTANDING AND COMPLIANCE AND |
| | STATE THAT THESE TWO COMMENTS WILL NOT AFFECT HEIGHT OR |
| | LOCATION OF THE FOUNDATION. SINCE THIS NEEDS ANOTHER |
| | BUILDING REVIEW DUE TO WRONG STRUCTURAL PAGES |
| | SUBMITTED, PLEASE PROVIDE AT TIME OF RESUBMITTAL IN |
| | "SUPPORTING DOCUMENTS". |
| | |
| | 12. WHEN RESUBMITTING, PLEASE REMOVE KITCHEN DESIGN |
| | PAGES; THESE SHEETS HAVE NOT BEEN REVIEWED AND SHOULD |
| | NOT BE A PART OF A FOUNDATION PERMIT. ALSO, IF |
| | POSSIBLE, RENAME THE THREE SITE PLANS WHICH APPEAR AT |
| | THE END OF SUBMITTAL DUE TO INCONSISTENT NAMING |
| | CONVENTION. THE SAME PAGES SUBMITTED FOR THE VERTICAL |
| | BUILDING PERMIT SHOULD BE SUBMITTED WITH THE SAME |
| | NAMES, SAME VERSION. ONE SITE PLAN IS DATED 6/1/2017; |
| | IS THIS CURRENT? PLEASE CORRELATE. |
| | |
| | 13. THE STRUCTURAL SHEETS IN THIS SUBMITTAL (FOR |
| | EXAMPLE, SHEET S0.02) WAS SEALED 10/2/17. AFTER THAT |
| | DATE, THERE WAS A DESIGN CHANGE (HEIGHT INCREASE) WHICH |
| | AFFECTED THE STRUCTURAL PAGES. MORE RECENT PAGES DATED |
| | 3/16/18 WERE UPLOADED TO THE VERTICAL BUILDING PERMIT. |
| | UPDATE ALL PAGES TO THE MOST CURRENT DESIGN. |
| | |
| | 14. THIS PERMIT WILL BE ISSUED WITH PROVISOS: |
| | |
| | A. COMPLIANCE WITH ART IN PUBLIC PLACES ORDINANCE |
| | 78-123 REQUIRED: MS. SYBILLE WELTER, 561-822-1515, |
| | [email protected]. MS. WELTER WILL ADVISE VIA EMAIL WHEN |
| | THIS IS COMPLETE. |
| | |
| | B. FBC 110.3.7.4.3 SHORING AND RESHORE ENGINEERING TO |
| | BE SUBMITTED AND REVIEWED PRIOR TO INSTALLATION. |
| | FAILURE TO SUBMIT SHORING/RESHORE ENGINEERING TIMELY |
| | WILL RESULT IN A STOP WORK ORDER. AN ENGINEERED |
| | GUARDRAIL DETAIL (CONSTRUCTION IN PROGRESS) IS ALSO |
| | REQUIRED PRIOR TO INSTALLATION. |
| | |
| | C. FBC 105.13 PHASED PERMIT APPROVAL. AFTER SUBMITTAL |
| | OF THE APPROPRIATE CONSTRUCTION DOCUMENTS, THE BUILDING |
| | OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE |
| | CONSTRUCTION OF FOUNDATIONS OR ANY OTHER PART OF A |
| | BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS |
| | FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN |
| | SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION |
| | OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED |
| | AT THE HOLDER?S OWN RISK WITH THE BUILDING OPERATION |
| | AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE |
| | STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED |
| | TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS |
| | PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE, ALL |
| | OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST |
| | BE SECURED PRIOR TO THIS PROVISION BEING APPLIED. |
| | |
| | D. THE LIFE SAFETY SHEETS WERE NOT THOROUGHLY REVIEWED. |
| | THIS WILL BE REVIEWED UNDER THE BUILDING PERMIT |
| | APPLICATION; FOUNDATION PERMIT WILL BE ISSUED AT |
| | APPLICANT'S RISK. |
| | |
| | E. ENERGY CALCS HAVE BEEN VOIDED AS THEY ARE NOT |
| | CORRECT AND ARE INCOMPLETE. SUBMIT WITH VERTICAL |
| | BUILDING PERMIT. |
| | |
| | F. SUBMIT RECORDED REPLAT PRIOR TO C.O. THE BOOK/PAGE |
| | MAY BE SENT VIA EMAIL. |
| | |