Plan Review Notes
Plan Review Notes For Permit 17010911
Permit Number 17010911
Review Stop B
Sequence Number 3
Notes
Date Text
2017-06-06 10:54:18****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 W. P. B. PERMIT: 17010911 (HOTEL FOUNDATION)
 ADD: 3200 N. CONGRESS AVE. (ADDRESS TO BE ASSIGNED)
 CONT: HEDRICK BROTHERS
 TEL: 561-689-8880
 E-MAIL: [email protected]
  
 FROM PREVIOUS LIST:
  
 1. SEE THRESHOLD REVIEW.
  
 3. SOIL BEARING VALUES; 2014 FBC-B 1803.3
  
 2ND REVIEW, NOT ADDRESSED. PROVIDE A CURRENT REPORT.
 HAVE SEOR INCORPORATE A SPECIFIC REFERENCE TO THE
 UPDATED SOILS REPORT ON THE PLAN, OR PROVIDE A SHOP
 DRAWING REVIEW OF THE SOILS REPORT.
  
 3RD REVIEW, RESPONSE LETTER STATES "SEE ATTACHED FROM
 UNIVERSAL ENGINEERS." IT IS NOT CLEAR HOW THIS COMMENT
 HAS BEEN ADDRESSED. SEE SHEET S0.00,
 310000-FOUNDATIONS, REVISE TO INCORPORATE GEOTECHNICAL
 REPORT (CURRENTLY "XXXX").
  
 4. SEE SIGNATURE REVIEW.
  
 5. 2ND REVIEW, SET BACK/ SEPARATION FROM PROPOSED
 BUILDING TO PROPERTY LINE(S) AND TO ASSUMED PROPERTY
 LINES IS REQUIRED, FBC B 705.3. DEPENDING ON THE
 LOCATION OF THE PROPERTY LINES AND/OR ASSUMED PROPERTY
 LINES, INFORMATION REGARDING AFFECTED BUILDINGS OR
 PROPOSED BUILDINGS MAY ALSO BE REQUIRED.
  
 A NOTE ON THE PLANS (A0.0.02) STATES THAT THIS BUILDING
 IS OVER 30 FEET FROM OTHER BUILDINGS AND/OR LOT LINES.
 IT IS NOT CLEAR WHERE THE PROPERTY LINES ARE LOCATED.
 DISTANCE BETWEEN BUILDINGS NOT CLEAR (FOR INSTANCE -
 PROPOSED HOTEL TO BUILDING 11 ON SHEET C2, PROPOSED
 HOTEL TO PARKING GARAGE, HOTEL TO CLUBHOUSE), LOCATION
 OF ASSUMED PROPERTY LINE(S) NOT CLEAR.
  
 3RD REVIEW, RESPONSE LETTER HAS NO RESPONSE FOR THIS
 ITEM. IT IS NOT CLEAR HOW THIS ITEM HAS BEEN ADDRESSED.
  
 FOR INSTANCE - A NOTE ON THE PLAN STATES "EXTERIOR
 OPENING PROTECTION: BUILDING SEPARATION >/=20' NO
 LIMIT." ALTHOUGH THE NOTE STATES THAT THE BUILDING IS
 OVER 30' FROM OTHER BUILDINGS AND/OR LOT LINES, IT IS
 NOT CLEAR WHERE THE ASSUMED PROPERTY LINE, OR THE
 PROPERTY LINE IS LOCATED. SEE ALSO 107.3.5.1.1(1),SET
 BACK/SEPARATION (ASSUMED PROPERTY LINES).
  
 6. OK
  
 7. SEE SIGNATURE REVIEW.
  
 8. SEE IMPACT FEE REVIEW.
  
 9. OK
  
 10. FS471, FS481, ARCHITECTS AND ENGINEERS HAVE
 REQUIREMENTS TO HAVE A TITLE BLOCK ON EACH SHEET WHICH
 INCLUDES THE PRINTED NAME AND LICENSE NUMBER, COMPANY
 LICENSE NUMBER (AS WELL AS OTHER INFORMATION).
  
 STRUCTURAL ENGINEER OF RECORD HAS A COMPLIANT TITLE
 BLOCK ON ALL S SHEETS. HOWEVER, REGARDING THE
 ARCHITECTURAL SHEETS, IT NOT CLEAR WHO IS SEALING THESE
 SHEETS. THE ARCHITECTURAL SHEETS LACK A TITLE BLOCK.
 THERE IS A BAR WITH ALL OF THE DESIGN PROFESSIONALS.
 THE ENGINEER'S NAME IS IN THE "SEAL" BLOCK. REVISE
 ARCHITECTURAL SHEETS TO INCLUDE ALL INFORMATION
 REQUIRED BY FAC61G16, FS481.
  
 3RD REVIEW: ENGINEER'S NAME WAS REMOVED FROM THE
 SHEETS, ARCHITECT'S NAME DID NOT REPLACE ENGINEER'S
 NAME. FOR EXAMPLE, SEE SHEET A0.0.02; THIS SHEET IS
 REQUIRED TO BE SIGNED AND SEALED AS IT IS REQUIRED TO
 DEMONSTRATE CODE COMPLIANCE. SEE FS481, A TITLE BLOCK
 FOR THE ARCHITECT IS REQUIRED, INCLUDING THE
 ARCHITECT'S PRINTED NAME AND LICENSE NUMBER, ARCHITECT
 BUSINESS LICENSE NUMBER. THIS COMMENT APPLIES TO OTHER
 (POSSIBLY ALL) A SHEETS.
  
 SEE SHEET A0.0.02; "APPLICABLE CODES" INCLUDES A
 REFERENCE TO THE BROWARD COUNTY AMENDMENTS TO THE FFPC,
 REVISE.
  
 THRESHOLD STATEMENT FOR A SHEETS LACK A REFERENCE TO
 THE BUILDING CODE; REVISE.
  
 11. OK
  
 12. FROM FIRST REVIEW: IF CIVIL SHEETS ARE USED TO SHOW
 COMPLIANCE WITH FLORIDA BUILDING CODE, THE ADVANCED
 BUILDING CODE COURSE IS REQUIRED FOR THE ENGINEER,
 FS471.0195.
  
 2ND REVIEW, NOT CLEAR IF THIS IS REQUIRED AS COMMENT #5
 WAS NOT ADDRESSED.
  
 FROM FIRST REVIEW: THE DBPR WEBSITE
 (WWW.MYFLORIDALICENSE.COM) DOES NOT SHOW THAT JORGE
 REYES, PE HAS TAKEN THE ADVANCED BUILDING CODE COURSE,
 PLEASE ADDRESS.
  
 2ND REVIEW, NOT CLEAR HOW THIS WAS ADDRESSED. AN EMAIL
 WAS SENT TO MR. REYES ON 6/6.
  
 13. THIS PERMIT WILL BE ISSUED WITH PROVISOS:
  
 A. COMPLIANCE WITH ART IN PUBLIC PLACES ORDINANCE
 78-123 REQUIRED: MS. SYBILLE WELTER, 561-822-1515,
 [email protected]. MS. WELTER WILL ADVISE VIA EMAIL WHEN
 THIS IS COMPLETE.
  
 B. FBC 110.3.7.4.3 SHORING AND RESHORE ENGINEERING TO
 BE SUBMITTED AND REVIEWED PRIOR TO INSTALLATION.
 FAILURE TO SUBMIT SHORING/RESHORE ENGINEERING TIMELY
 WILL RESULT IN A STOP WORK ORDER. AN ENGINEERED
 GUARDRAIL DETAIL (CONSTRUCTION IN PROGRESS) IS ALSO
 REQUIRED PRIOR TO INSTALLATION.
  
 C. FBC 105.13 PHASED PERMIT APPROVAL. AFTER SUBMITTAL
 OF THE APPROPRIATE CONSTRUCTION DOCUMENTS, THE BUILDING
 OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE
 CONSTRUCTION OF FOUNDATIONS OR ANY OTHER PART OF A
 BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS
 FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN
 SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION
 OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED
 AT THE HOLDER?S OWN RISK WITH THE BUILDING OPERATION
 AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED
 TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS
 PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE, ALL
 OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST
 BE SECURED PRIOR TO THIS PROVISION BEING APPLIED.
  
 D. THE LIFE SAFETY SHEETS WERE NOT THOROUGHLY REVIEWED.
 THIS WILL BE REVIEWED UNDER THE BUILDING PERMIT
 APPLICATION; FOUNDATION PERMIT WILL BE ISSUED AT
 APPLICANT'S RISK.
  
 E. ENERGY CALCS WERE NOT THOROUGHLY REVIEWED. WHEN
 RESUBMITTING THE BUILDING, ADDRESS THE FOLLOWING:
 WATER HEATER COMPLIANCE IS BLANK
 NO DOORS SHOWN
 CHECK ALL
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved