| 2017-02-15 08:21:59 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA RES BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 |
| | COMMENTS: |
| | |
| | 1. PROVIDE AIC CALCULATIONS FOR NEW SERVICE SHOWN. FBC |
| | 107.3.5 |
| | 2. GENERAL NOTE TO INDICATED REQUIRED SEPARATE PERMITS |
| | FOR LOW VOLTAGE SYSTEMS. FBC 107.3.5 |
| | 3. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE |
| | PER FBC RES E3609.3 |
| | 4. PLEASE ADDRESS WALL SPACE RECEPTACLE REQUIREMENTS |
| | PER FBC RES E3901.2.2, 1. ANY SPACE THAT IS 2FT OR MORE |
| | IN WIDTH. SEE BEDROOM WALLS ADJACENT TO NEW CLOSET. |
| | 5. SHOW A RECEPTACLE W/P GFCI PROTECTED AT THE HVAC AC |
| | LOCATION FOR SERVICE PER FBC RES E3901.12 HVAC OUTLET |
| | 6. PROVIDE A NOTE PER FBC ENERGY CONSERVATION CODE TO |
| | INDICATE; 75% OF LAMPS TO HIGH EFFICACY LAMPS. |
| | 7. PLEASE SHOW ON PANELBOARD 20A CIRCUITS REQUIRED FOR |
| | LAUNDRY ROOM 1500VA. FBC RES E3703.2 AND 4 |
| | 8. ARC FAULT REQUIMENTS SHALL APPLY TO ALL AREAS AS |
| | NOTED ON FBC RES E3902.12 |
| | 9. UPDATE ALL CODE REFERENCES TO NEC 2011 NOT 2005. SEE |
| | ABOVE CODES IN EFFECT. |
| | 10. PROVIDE A NOTE TO COMPLY WITH TAMPER RESISTANT |
| | RECEPTACLES PER FBC RES 4002.14 |
| | 11. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY |
| | QUESTIONS OR CONCERNS. |
| | |
| | |
| | VALENTINO PEREZ |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6717 |
| | |