| 2017-08-17 16:51:34 | 2ND REVIEW FBC-2014 RESIDENTIAL. |
| | PERMIT #17010898 |
| | 8/17/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | SOME OF THE 1ST REVIEW COMMENTS STILL EXIST. I HAVE |
| | REPRINTED THEM BELOW WITH ADDITIONAL COMMENTS AND |
| | CLARIFICATIONS. |
| | |
| | 1) PROVIDE A SCOPE OF WORK FOR MECHANICAL ALTERATIONS |
| | WITH CORRESPONDING DRAWINGS AND DETAILS ON THE PLAN. |
| | |
| | NEW COMMENT: THE REVISED PLAN IS INDICATING A REPLACED |
| | AIR HANDLER. PLEASE PROVIDE ON THE PLAN AN AC EQUIPMENT |
| | SCHEDULE THAT INCLUDES THE AIR HANDLER AND THE |
| | CONDENSER, AND SUBMIT AN AHRI CERTIFICATE FOR THE |
| | SYSTEM- SECTION R101.4.7 FBC-14 ENERGY CONSERVATION. |
| | |
| | NEW COMMENT: THE LOCATION OF THE AIR HANDLER APPEARS TO |
| | HAVE CHANGED. PLEASE SHOW ALL ALTERATIONS TO THE |
| | EXISTING SUPPLY AND RETURN SYSTEM, AND INDICATE THE |
| | REQUIRED CLEARANCES FOR THE AIR HANDLER IN THE CLOSET |
| | AS REQUIRED BY SECTION M1305.1.1. |
| | |
| | NEW COMMENT: THE LOCATION OF THE CONDENSER APPEARS TO |
| | HAVE CHANGED. PLEASE PROVIDE STRUCTURAL DETAILS FOR |
| | INSTALLATION OF THE PAD AND MOUNTING OF THE CONDENSER |
| | TO THE PAD- SECTION M1305.1.4.1 & M1307.2 FBC-14 |
| | RESIDENTIAL. |
| | |
| | 2) SUBMIT DOCUMENTATION OF ENERGY CONSERVATION |
| | COMPLIANCE AS REQUIRED BY SECTIONS R101.4.3, R101.5.1 |
| | FBC-14 ENERGY CONSERVATION CODE. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |