| Plan Review Notes For Permit 17010898 |
| Permit Number |
17010898 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-02-09 07:43:44 | 1ST REVIEW FBC-2014 RESIDENTIAL. | | | PERMIT #17010898 | | | 2/9/17 | | | | | | 1) PROVIDE A SCOPE OF WORK FOR MECHANICAL ALTERATIONS | | | WITH CORRESPONDING DRAWINGS AND DETAILS ON THE PLAN. | | | CLARIFY IF THE EXISTING AC SYSTEM WILL BE REPLACED OR | | | ALTERED AS PART OF THE RENOVATION. | | | | | | 2) INDICATE HOW THE BATHROOMS WILL BE VENTILATED USING | | | EITHER OPERABLE OPENINGS TO THE OUTDOORS PER SECTION | | | R303.3, OR MECHANICALLY PER M1507.4. | | | | | | 3) PROVIDE EXHAUST VENTILATION FOR THE KITCHEN- SEE | | | SECTIONS M1503- M1507 FOR COMPLIANCE METHODS. | | | | | | 4) THE PLAN INDICATES A FIREPLACE THAT APPEARS TO BE A | | | NEW INSTALLATION. PLEASE PROVIDE AN EQUIPMENT SCHEDULE | | | ON THE PLAN THAT LISTS THE MAKE AND MODEL OF THE UNIT, | | | AND TYPE- GAS-FIRED, WOOD BURNING, ELECTRIC ETC. A) | | | SUBMIT MANUIFACTURER'S SPECIFICATIONS FOR THE UNIT AND | | | THE VENT SYSTEM. B) PROVIDE A VENTING DIAGRAM THAT | | | INDICATES THE TYPE AND SIZE OF VENT MATERIAL, LENGTH OF | | | VENT | | | | | | RUN AND LOCATION OF VENT TERMIANTION CAP. | | | | | | 5) SUBMIT DOCUMENTATION OF ENERGY CONSERVATION | | | COMPLIANCE AS REQUIRED BY SECTIONS R101.4.3, R101.5.1 | | | FBC-14 ENERGY CONSERVATION CODE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|