| 2017-02-02 07:25:51 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17010886 | | | 2/2/17 | | | | | | 1) THE AC EQUIPMENT SCHEDULE INDICATES NO HEATING DATA | | | FOR AHU-4, HOWEVER HEAT IS REQUIRED FOR THE CLUBHOUSE | | | PER SECTION 309.1 PLEASE NOTE THE SUBMITTED AC | | | CALCULATIONS INDICATE 10.1 MBH CENTRAL HEATING COIL | | | SIZING DATA. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|