| 2017-03-07 15:37:46 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | |
| | |
| | 1) EOR 61G DOCUMENTS ARE REQUIRED TO BE WITH THIS |
| | PERMIT AND WILL ALLOOWED TO BE SUBMITTED AS A REVISION |
| | TO THIS PERMIT, BUT PRIOR TO THE SHOP DRAWINGS |
| | SUBMITTAL. |
| | |
| | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, |
| | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | PLEASE DO NOT MISUNDERSTAND AND ENSURE COMPLIANCE WITH |
| | THE ABOVE. |
| | |
| | |
| | |
| | 2) A MONITORED FIRE ALARM SYSTEM IS REQUIRED TO MONITOR |
| | THE FIRE SPRINKLER SYSTEM PER NFPA 101, 5TH EDITION. |
| | |
| | 12.3.4.1.2 ASSEMBLY OCCUPANCIES THAT ARE A PART OF A |
| | MULTIPLE OCCUPANCY PROTECTED AS A MIXED OCCUPANCY (SEE |
| | 6.1.14) SHALL BE PERMITTED TO BE SERVED BY A COMMON |
| | FIRE ALARM SYSTEM, PROVIDED THAT THE INDIVIDUAL |
| | REQUIREMENTS OF EACH OCCUPANCY ARE MET. |
| | |
| | |
| | PLEASE PROVIDE A FIRE ALARM FOR MONIORTING THE FIRE |
| | SPRINKLER SYSTEM. |
| | |
| | |