| Date |
Text |
| 2017-02-16 10:53:49 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1. THIS APPEARS TO BE A CHANGE OF OCCUPANCY, FBC EB |
| | CHAPTER 10. REVISE PLAN TO SHOW COMPLIANCE. NO |
| | INFORMATION REGARDING BUILDING AREA FBC TABLE 503 WAS |
| | PROVIDED. |
| | |
| | REVISE PLAN TO INCLUDE INFORMATION REGARDING THE OTHER |
| | TENANT SPACES, INCLUDING SF AREA AND OCCUPANCY |
| | CLASSIFICATION, AND BUILDING TYPE FBC CHAPTER 6. |
| | |
| | REVISE PLAN TO INCLUDE PREVIOUS OCCUPANCY, FBC EB 1012, |
| | TABLES 1012.4, 1012.5, 1012.6. |
| | |
| | REVISE PLAN TO SHOW COMPLIANCE WITH ALL CHANGE OF |
| | OCCUPANCY REQUIREMENTS FBC EB 1012. |
| | |
| | NO SITE PLAN PROVIDED; THIS WILL LIKELY BE REQUIRED FBC |
| | EB TABLE 1012.6. |
| | |
| | 2. THIS APPEARS TO BE A NON SPRINKLERED BUILDING. |
| | SPRINKLERS ARE PROPOSED. SEE FIRE COMMENTS; THIS IS |
| | ALSO APPLICABLE FOR BUILDING. IF THE BUILDING IS |
| | CURRENTLY FULLY SPRINKLERED, REVISE PLAN TO STATE. IF A |
| | NEW SPRINKLER SYSTEM IS PROPOSED, PROVIDE SPRINKLER |
| | INFORMATION. |
| | |
| | IF A NEW SPRINKLER SYSTEM IS PROPOSED, AN ENGINEERING |
| | PERMIT IS REQUIRED. CONTACT ENGINEERING DEPARTMENT AND |
| | SUBMIT ANY REQUIRED APPLICATIONS. |
| | |
| | 3. PROVIDE SPEC SHEETS AND INSTALLATION INSTRUCTIONS |
| | FOR THE MILL, FBC 107. |
| | |
| | 4. DETAIL 13-A9.0, THE FOOT REST APPEARS TO OBSTRUCT |
| | THE REQUIRED TOE CLEARANCE, FBC A 306.2. REVISE PLAN TO |
| | SHOW COMPLIANCE. |
| | |
| | 5. REVISE PLAN TO INCLUDE FINISHED FLOOR ELEVATION, FBC |
| | B 1612. THIS IS CONSIDERED A SUBSTANTIAL IMPROVEMENT. |
| | |
| | 6. PROVIDE A SITE PLAN OR SURVEY WHICH INCLUDES ALL |
| | EQUIPMENT AT GRADE. IF ALL EQUIPMENT SERVICING THE |
| | BUILDING IS LOCATED ON THE ROOF, REVISE PLAN TO NOTE, |
| | FBC B 1612. |
| | |
| | 7. SHEET A7.0 INCLUDES A NOTE REGARDING PANIC HARDWARE. |
| | SEE FBC B 1008.1.10; WILL BOTH EXIT DOORS INCLUDE PANIC |
| | BARS? REVISE PLAN TO CLARIFY. |
| | |
| | 8. PLAN SPECIFIES TRULITE STOREFRONT SYSTEM AND DOORS, |
| | OVERHEAD DOORS. PROVIDE PRODUCT APPROVALS, FBC 107. ANY |
| | PRODUCT APPROVALS NOT SUBMITTED PRIOR TO PERMIT |
| | ISSUANCE WILL REQUIRE A REVISION, WITH ADDITIONAL FEES, |
| | TO BE SUBMITTED AND APPROVED PRIOR TO INSTALLATION. |
| | |
| | 9. SEE IMPACT FEE REVIEW. |
| | |
| | THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING PROVISO: |
| | |
| | MEANS OF EGRESS ILLUMINATION IN COMPLIANCE WITH FBC B |
| | 1006 REQUIRED, INCLUDING THE EXIT DISCHARGE TO THE |
| | PUBLIC WAY. |
| | |
| | A "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE WILL BE |
| | REQUIRED. THIS SHOULD INCLUDE ALL EQUIPMENT SERVICING |
| | THE BUILDING. |
| | |