| 2017-01-30 06:31:26 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17010882 |
| | ADD: 4047 OKEECHOBEE BLVD. SUITE # 108. |
| | CONT: MOSS DEVCO INC. |
| | TEL:561-876-4570 |
| | E-MAIL: |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JAN. 30/2017 |
| | ACTION: DENIED |
| | |
| | 1 SHEET S-1 DISCREPANCY IN PLANS. 107.2.1.3 ADDITIONAL |
| | INFORMATION REQUIRED. 2014 FBC-B TABLE 603 RATINGS ON |
| | THE ROOF FRAMING MEMBERS. THE SHEET S-1 INDICATES THE |
| | TYPE OF CONSTRUCTION AS A BUILDING TYPE I-A REQUIRING 1 |
| | 1/2 HOUR FIRE RATING, THE SHEET S-1 INDICATES THE |
| | BUILDING IS FIRE SPRINKLERED, UNPROTECTED BOTH IA AND |
| | IB HAVE FIRE PROTECTED ROOF FRAMING MEMBERS. UNDER THE |
| | HEADING OF CONSTRUCTION LISTED: 1 STORY CBS WITH METAL |
| | JOIST TYPE IIB NOT REQUIRING ANY FIRE PROTECTION ON THE |
| | ROOF FRAMING MEMBERS OR SECONDARY MEMBERS. PLEASE |
| | IDENTIFY THE TYPE OF CONSTRUCTION AND CORRECT THE PLANS |
| | ACCORDINGLY. |
| | |
| | 2)SHEET S1 THE SQUARE FOOTAGE OF THIS TENANT SPACE IS |
| | 980 SQ. FT. THE OCCUPANCY TYPE IS LABELED BUSINESS. |
| | WITHIN THE TENANT SPACE THERE ARE (2) ROOMS LABELED |
| | CLASSROOMS, WITHIN THESE ROOMS THE OCCUPANT LOAD TAKEN |
| | SHOULD BE 15 SQ. FT./ OCCUPANT THIS WILL INCREASE THE |
| | OCCUPANT LOAD FOR THE OFFICE AND TEACHING PORTIONS OF |
| | THE OFFICE TO BE 27 OCCUPANTS.2014 FBC-B TABLE 1004.1.2 |
| | BUSINESS 100 GROSS AND EDUCATIONAL |
| | IS TAKEN AT 15 NET. |
| | |
| | 3) SHEET S2 ON THE RIGHT SIDE OF THE UNIT UNDER PERMIT |
| | IS A NOTE; NEW ONE HOUR PARTY WALLS (BY OTHERS). ARE |
| | THESE NEW WALLS FURTHER SEPARATING THE BUILDING INTO |
| | SMALLER BUT MORE BUILDINGS? PARTY WALLS ARE FIRE WALLS. |
| | 706.1.1 PARTY WALLS. ANY WALL LOCATED ON A LOT LINE |
| | BETWEEN ADJACENT BUILDINGS, WHICH IS USED OR ADAPTED |
| | FOR JOINT SERVICE BETWEEN THE TWO BUILDINGS, SHALL BE |
| | CONSTRUCTED AS A FIRE WALL IN ACCORDANCE WITH SECTION |
| | 706. PARTY WALLS SHALL BE CONSTRUCTED WITHOUT OPENINGS |
| | AND SHALL CREATE SEPARATE BUILDINGS. |
| | THESE WALLS WILL NEED TO BE PERMITTED AND COMPLETED |
| | BEFORE THE TENANT PERMITS CAN BE PERMITTED AND |
| | CERTIFICATE OF COMPLETION CAN OCCUR. |
| | |
| | 4) SHEET S3 IS THE LIFE SAFETY PLAN, PLEASE PROVIDE THE |
| | LIFE SAFETY PLAN SHOULD HAVE ALL OF THE FURNITURE SHOWN |
| | ON THE PLANS. 107.3.5.1.1. MINIMUM PLAN REVIEW CRITERIA |
| | FOR COMMERCIAL BUILDING PLAN REVIEW, |
| | BUILDING. |
| | |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |