Plan Review Notes
Plan Review Notes For Permit 17010872
Permit Number 17010872
Review Stop P
Sequence Number 3
Notes
Date Text
2017-08-17 11:11:572ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 2ND REQUEST1. PLEASE PROVIDE GREASE INTERCEPTOR SIZING
 CALCULATIONS. PER WPB AMEND TO FBC 107.2.1 I SUGGEST
 HAVING THE MANUFACTURE DO YOUR CALCULATIONS YOU MIGHT
 FIND YOU CAN USE A SMALLER TANK.
  
 2. THE OUTLET OF GREASE INTERCEPTOR IS SHOWN AT 4" THE
 INLET OF THE SUMP PUMP SHOWS 3" THE SANITARY PIPING CAN
 NOT BE REDUCED IN THE DIRECTION OF FLOW. PER FBC PL
 704.2
  
 3. PLEASE PROVIDE MANUFACTURE SPEC FOR SUMP PUMP
 SHOWING THE FLOW RATE. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  