2017-07-05 15:27:433RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17010872
 7/5/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) CLARIFY HOW ACCESS FOR SERVICE AND REPLACEMENT OF
 THE ABOVE CEILING AIR HANDLERS WILL BE PROVIDED-
 SECTION 306.1. SHOW PANEL LOCATIONS AND PROVIDE
 DIMENSIONS.
  
 306.1 ACCESS FOR MAINTENANCE AND REPLACEMENT.
 APPLIANCES SHALL BE ACCESSIBLE FOR INSPECTION, SERVICE,
 REPAIR AND REPLACEMENT WITHOUT DISABLING THE FUNCTION
 OF A FIRE-RESISTANCE-RATED ASSEMBLY OR REMOVING
 PERMANENT CONSTRUCTION, OTHER APPLIANCES, VENTING
 SYSTEMS OR ANY OTHER PIPING OR DUCTS NOT CONNECTED TO
 THE APPLIANCE BEING INSPECTED, SERVICED, REPAIRED OR
 REPLACED. A LEVEL WORKING SPACE AT LEAST 30 INCHES DEEP
 AND 30 INCHES WIDE (762 MM BY 762 MM) SHALL BE PROVIDED
 IN FRONT OF THE CONTROL SIDE TO SERVICE AN APPLIANCE.
  
 2) SHEET D1: PROVIDE HVAC DEMOLITION NOTES. IT APPEARS
 THAT THE EXISTING AIR HANDLER IN THE CORRIDOR CLOSET IS
 BEING REMOVED AND THE CLOSET OPENING WALLED OFF. REFER
 TO COMMENT #1 ABOVE AND CLARIFY HOW THE OWNER OF THE
 UNIT WILL GAIN ACCESS TO IT.
  
 3) M0.1: REVISE SCOPE OF WORK #3 TO INDICATE THAT
 SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN EXHAUST
 SYSTEM AND WALK-IN COOLER. PLEASE NOTE THAT THE
 LOCATION OF THE GREASE HOOD EXHAUST TERMINATION AT THE
 SOUTH WALL MAY NOT BE IN COMPLIANCE WITH SECTION
 506.3.13.2
  
 4) M1.1: PLEASE LABEL THE O/A INTAKE OPENING IN THE
 SIDEWALK AS EITHER NEW OR EXISTING.
  
 5) M1.1: REVISE MECHANICAL PLAN KEY NOTE #1: SECTION
 401.4 FBC-14 MECHANICAL REQUIRES A MINIMUM 10'
 CLEARANCE FROM THE O/A OPENING TO THE STREET, WHICH IS
 ALSO NOTED ON THE PLAN.
  
 6) M1.1: INDICATE HOW ACCESS TO THE FIRE DAMPER IN THE
 FLOOR WILL BE PROVIDED- SECTION 607.4.
  
 7) M1.1: PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION
 OF THE NEW ROOFTOP CONDENSERS- SECTION 301.15. SEE ALSO
 BUILDING REVIEW COMMENTS.
  
 8) M1.1: IT APPEARS FROM THE DRAWINGS THAT GUARDS WILL
 BE REQUIRED ALONG THE ROOF EDGES IN THE AREA OF THE NEW
 ROOFTOP CONDENSERS. PLEASE SEE SECTION 304.11 AND
 PROVIDE DETAILS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  