Plan Review Notes
Plan Review Notes For Permit 17010872
Permit Number 17010872
Review Stop E
Sequence Number 3
Notes
Date Text
2017-07-11 14:56:23CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. SHEET E3.1 SHOWS THE CONDUCTOR SIZE FOR THE FEED
 FROM THE EXISTING WIREWAY TO THE METER, FROM THE METER
 TO THE DISCONNECT, AND FROM THE DISCONNECT TO THE PANEL
 AS SIZE 3/0 COPPER. 3/0 IS NOT RATED FOR THE LOAD
 SPECIFIED IN THE LOAD CALCULATION. PROVIDE CORRECT WIRE
 AND CONDUIT SIZE TO HANDLE THE LOAD. NEC 310.15(B)(16),
 NEC CHAPTER 9 TABLES.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  