| 2017-06-29 15:07:18 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17010872 |
| | ADD: 120 S. OLIVE AVE. SUITE 102 |
| | CONT: VILLA FRANCA DESIGN & DEVELOPMENT |
| | TEL: 561-575-2288 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: THURS. JUNE 29/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A8 & M1.1. THE NEW DESIGN OF THE TENANT SPACE |
| | WILL REQUIRE REVISIONS TO THE PLANS FOR THE AIR |
| | HANDLIER LOCATION THAT SERVES THE CORRIDOR. THE |
| | MECHANICAL PLANS SHOW A HORIZONTAL UNIT WHERE THE OLD |
| | SET OF PLANS SHOWED A VERTICAL AIR HANDLER WITHIN A A/ |
| | C CLOSET WITHIN THE CORRIDOR. THE NEW LOCATION SHOWS |
| | THE AIR HANDLIER OVER THE RESTROOM WITH A HARD CEILING |
| | WITH A 24X36 ACCESS PANEL OUTSIDE OF THE RESTROOM. |
| | PLEASESHOW A CUT SECTION ABOVE THE CEILING WHERE THE |
| | ACCESS PANEL IS TO WHERE THE CORRIDOR AIR HANDLER IS |
| | INSTALLED, PLEASE SHOW ALL DUCTS IN THE VACINITY, |
| | PLEASE ALSO NOT THEIR IS AN ELECTRICLA PANEL IN THE |
| | RESTROOM WALL THAT MAY HAVE CONDUITS IN CONFLICT WITH |
| | ACCES TO THIS UNIT. |
| | 2014 FBC-B- 2801.1 MECHANICAL APPLIANCES, EQUIPMENT AND |
| | SYSTEMS SHALL BE CONSTRUCTED, INSTALLED AND MAINTAINED |
| | IN ACCORDANCE WITH THE FLORIDA BUILDING CODE & |
| | MECHANICAL CODE. |
| | |
| | 2) SHEET M1.1 SHOWS NEW A/C CONDENSING UNITS INSTALLED |
| | ON A NEW ROOF TOP A/C STAND. PLEASE PROVIDE THE PRODUCT |
| | APPROVAL FOR THE STAND AND ANCHORING OF THE STAND AND |
| | OF THE A/C UNITS TO THE STAND. FOR ALL ROOF TOP |
| | EQUIPMENT, CURBS OR A/C STANDS, DETAILED ATTACHMENT TO |
| | THE ROOF FRAMING & DECK AS WELL AS FROM THE CURB OR |
| | ROOF STAND TO THE EQUIPMENT ABOVE. |
| | |
| | 2A) 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE |
| | 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY |
| | OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(G) PRE-ENGINEERED A/C STANDS |
| | |
| | 2B) THE ROOF TOP PRODUCT APPROVAL FOR A/C STANDS WILL |
| | BE REQUIRED TO BE REVIEWED BY THE DESIGNER OF RECORD |
| | BEFORE BEING SUBMITTED TO THE BUILDING DEPARTMENT. |
| | EITHER THE CONTRACTOR OR THE DESIGNER OF RECORD WILL |
| | NEED TO IDENTIFY/ CIRCLE THE FOLLOWING CRITERIA, |
| | CALCULATING THE AREA OF THE ROOF TOP COMPRESSORS, THE |
| | MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT, |
| | CIRCLED THE DESIGN PARAMETERS IN THE TABLES , ANCHORS |
| | AND UPLIFT VERSES MOMENT. |
| | |
| | 2C) SHEET M1.1 INDICATES THE NEW A/ C COMPRESSORS AND |
| | STAND WILL BE ON A 3RD FLOOR ROOF. PLEASE PROVIDE |
| | COMPLIANCE WITH; |
| | 1013.6 MECHANICAL EQUIPMENT. |
| | GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT, |
| | FANS, ROOF HATCH OPENINGS OR OTHER COMPONENTS THAT |
| | REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF |
| | A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH |
| | EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762 |
| | MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD |
| | SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A |
| | SPHERE 21 INCHES (533 MM) IN DIAMETER. THE GUARD SHALL |
| | EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND EACH END |
| | OF SUCH APPLIANCE, EQUIPMENT, FAN OR COMPONENT. |
| | |
| | 3) PLEASE PROVIDE HOW THE A/ C COMPRESSOR PIPES ARE |
| | GOING TO BE ROUTED FROM THE 3RD FLOOR ROOF TO THE 1ST |
| | FLOOR. PLEASE PROVIDE COMPLIANCE WITH 2014 FBC-B |
| | 714.4.1 714.4.1 FIRE-RESISTANCE-RATED ASSEMBLIES. |
| | PENETRATIONS OF THE FIRE-RESISTANCE-RATED FLOOR, |
| | FLOOR/CEILING ASSEMBLY OR THE CEILING MEMBRANE OF A |
| | ROOF/CEILING ASSEMBLY SHALL COMPLY WITH SECTIONS |
| | 714.4.1.1 THROUGH 714.4.1.3. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |