Plan Review Notes
Plan Review Notes For Permit 17010872
Permit Number 17010872
Review Stop P
Sequence Number 2
Notes
Date Text
2017-07-11 10:10:021ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE OTHER FIXTURES IN KITCHEN AREA SHALL BE
 CONNECTED TO THE GREASE INTERCEPTOR, THE FLOOR DRAIN
 AND FLOOR SINKS AND THE PREP SINK. PER FBC PL 1003.3.1
  
 2. PLEASE PROVIDE GREASE INTERCEPTOR CALCULATIONS. PER
 WPB AMEND TO FBC 107.2.1
  
 3. WITH A OCCUPANT LOAD OF 20 PEOPLE IT IS REQUIRED TO
 PROVIDE SEPARATE FACILITIES FOR EACH SEX. FBC PL 403.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  