| Notes |
| Date |
Text |
| 2017-03-14 17:40:50 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17010872 | | | 3/14/17 | | | | | | 1) REFER TO SECTION 401.5 AND SHOW THE ACTUAL LOCATION | | | OF THE O/A INTAKE ON THE PLAN WITH CLEARANCE DISTANCE | | | MEASUREMENTS. PLEASE NOTE THE OPENING MUST BE A MINIMUM | | | 10' FROM THE STREET. | | | | | | 2) THE SUBMITTED ENERGY FORM C402-2014 CANNOT BE USED | | | TO SHOW COMPLIANCE FOR A CHANGE OF OCCUPANCY. PLEASE | | | SEE THE HEADING AT THE TOP OF THE FORM AND SECTION | | | C101.5.1.1 FBC-14 ENERGY CONSERVATION. | | | | | | 3) THE NARRATIVE RESPONSE TO THE 1ST REVIEW COMMENT #4 | | | STATES "ALL ELECTRIC APPLIANCES, NO HOOD OR EXHAUST | | | REQUIRED" PLEASE NOTE THE EXHAUST RATE OF 0.7 CFMS PER | | | SQ. FT. IS REQUIRED REGARDLESS OF THE TYPE OF COOKING | | | APPLIANCES- GAS OR ELECTRIC. IN ADDITION PLEASE REFER | | | TO SECTION 507.2.1 FBC-14 MECHANICAL WHICH STATES A | | | TYPE 1 HOOD IS REQUIRED WHERE COOKING APPLIANCES | | | PRODUCE GREASE OR SMOKE. | | | | | | 4) THERE ARE MANUFACTURER'S SPECIFICATIONS SUBMITTED | | | FOR A VENTLESS HOOD. PLEASE PROVIDE THE MAKE AND MODEL | | | IN THE EQUIPMENT SCHEDULE ON SHEET A2 . ON THE | | | MECHANICAL PLANS PROVIDE THE EXHAUST RATE OF THE HOOD, | | | INDICATE HOW MAKEUP AIR WILL BE SUPPLIED, AND PROVIDE | | | AN AIR BALANCE CALCULATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|