2017-03-14 17:40:502ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17010872
 3/14/17
  
 1) REFER TO SECTION 401.5 AND SHOW THE ACTUAL LOCATION
 OF THE O/A INTAKE ON THE PLAN WITH CLEARANCE DISTANCE
 MEASUREMENTS. PLEASE NOTE THE OPENING MUST BE A MINIMUM
 10' FROM THE STREET.
  
 2) THE SUBMITTED ENERGY FORM C402-2014 CANNOT BE USED
 TO SHOW COMPLIANCE FOR A CHANGE OF OCCUPANCY. PLEASE
 SEE THE HEADING AT THE TOP OF THE FORM AND SECTION
 C101.5.1.1 FBC-14 ENERGY CONSERVATION.
  
 3) THE NARRATIVE RESPONSE TO THE 1ST REVIEW COMMENT #4
 STATES "ALL ELECTRIC APPLIANCES, NO HOOD OR EXHAUST
 REQUIRED" PLEASE NOTE THE EXHAUST RATE OF 0.7 CFMS PER
 SQ. FT. IS REQUIRED REGARDLESS OF THE TYPE OF COOKING
 APPLIANCES- GAS OR ELECTRIC. IN ADDITION PLEASE REFER
 TO SECTION 507.2.1 FBC-14 MECHANICAL WHICH STATES A
 TYPE 1 HOOD IS REQUIRED WHERE COOKING APPLIANCES
 PRODUCE GREASE OR SMOKE.
  
 4) THERE ARE MANUFACTURER'S SPECIFICATIONS SUBMITTED
 FOR A VENTLESS HOOD. PLEASE PROVIDE THE MAKE AND MODEL
 IN THE EQUIPMENT SCHEDULE ON SHEET A2 . ON THE
 MECHANICAL PLANS PROVIDE THE EXHAUST RATE OF THE HOOD,
 INDICATE HOW MAKEUP AIR WILL BE SUPPLIED, AND PROVIDE
 AN AIR BALANCE CALCULATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  