| Plan Review Notes For Permit 17010872 |
| Permit Number |
17010872 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-02-02 08:04:54 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17010872 | | | 2/2/17 | | | | | | 1) THE PROJECT IS CLASSIFIED AS A CHANGE OF OCCUPANCY | | | PER SECTION 506.1 FBC-14 EXISTING BUILDING CODE. SPACES | | | UNDERGOING A CHANGE OF OCCUPANCY THAT WOULD RESULT IN | | | AN INCREASE IN DEMAND FOR EITHER FOSSIL FUEL OR | | | ELECTRICAL ENERGY SHALL COMPLY WITH FBC-14 ENERGY | | | CONSERVATION- SEE SECTIONS C101.4.5 AND C401.2 AND | | | PROVIDE DOCUMENTATION OF COMPLIANCE. | | | | | | 2) THE A1 PLAN INDICATES A GAS-FIRED COOKING APPLIANCES | | | REQUIRING COMBUSTION AIR. REFER TO SECTION 304.1 FBC-14 | | | FUEL GAS AND INDICATE HOW THE COMBUSTION AIR WILL BE | | | SUPPLIED AND PROVIDE A CALCULATION. | | | | | | 3) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR | | | KITCHEN EXHAUST SYSTEMS, FIRE SUPPRESSION, AND WALK-IN | | | COOLERS AND FREEZERS- PLEASE PLACE A NOTE ON THE PLANS | | | ACCORDINGLY. | | | | | | 4) AN EXHAUST RATE OF 0.7 CFMS PER SF IS REQUIRED FOR | | | THE KITCHEN PER TABLE 403.3. PLEASE INDICATE HOW | | | COMPLIANCE WILL BE MET AND PROVIDE AN AIR BALANCE | | | CALCULATION THAT INCLUDES ALL EXHAUST RATES IN THE | | | SPACE. | | | | | | 5) THE 8X8 O/A DUCT IN THE CRAWLSPACE MUST HAVE AN | | | INSULATION VALUE OF MINIMUM R-4.2. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|