Plan Review Notes
Plan Review Notes For Permit 17010872
Permit Number 17010872
Review Stop M
Sequence Number 1
Notes
Date Text
2017-02-02 08:04:541ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17010872
 2/2/17
  
 1) THE PROJECT IS CLASSIFIED AS A CHANGE OF OCCUPANCY
 PER SECTION 506.1 FBC-14 EXISTING BUILDING CODE. SPACES
 UNDERGOING A CHANGE OF OCCUPANCY THAT WOULD RESULT IN
 AN INCREASE IN DEMAND FOR EITHER FOSSIL FUEL OR
 ELECTRICAL ENERGY SHALL COMPLY WITH FBC-14 ENERGY
 CONSERVATION- SEE SECTIONS C101.4.5 AND C401.2 AND
 PROVIDE DOCUMENTATION OF COMPLIANCE.
  
 2) THE A1 PLAN INDICATES A GAS-FIRED COOKING APPLIANCES
 REQUIRING COMBUSTION AIR. REFER TO SECTION 304.1 FBC-14
 FUEL GAS AND INDICATE HOW THE COMBUSTION AIR WILL BE
 SUPPLIED AND PROVIDE A CALCULATION.
  
 3) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR
 KITCHEN EXHAUST SYSTEMS, FIRE SUPPRESSION, AND WALK-IN
 COOLERS AND FREEZERS- PLEASE PLACE A NOTE ON THE PLANS
 ACCORDINGLY.
  
 4) AN EXHAUST RATE OF 0.7 CFMS PER SF IS REQUIRED FOR
 THE KITCHEN PER TABLE 403.3. PLEASE INDICATE HOW
 COMPLIANCE WILL BE MET AND PROVIDE AN AIR BALANCE
 CALCULATION THAT INCLUDES ALL EXHAUST RATES IN THE
 SPACE.
  
 5) THE 8X8 O/A DUCT IN THE CRAWLSPACE MUST HAVE AN
 INSULATION VALUE OF MINIMUM R-4.2.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  