| 2017-02-13 08:05:33 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 |
| | COMMENTS: |
| | |
| | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE |
| | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE |
| | PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL |
| | LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE |
| | ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, KITCHEN |
| | HOODS ETC. A NOTE WILL SUFFICE. |
| | 2. ADD A GENERAL NOTE TO PROVIDE PER FBC EC 405.7.4- |
| | COMPLETION DOCUMENTS PER CODE SECTION. FBC EC 405.7.3- |
| | VOLTAGE DROP |
| | 3. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO |
| | INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC |
| | 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE |
| | VERBIAGE IN CODE. |
| | 4. PROVIDE A NOTE TO INDICATE COMPLIANCE WITH FBC EC |
| | 405.2 AUTOMATIC LIGHTING CONTROL AND LIGHTING DENSITIES |
| | PER CODE SECTION. |
| | 5. PROVIDE SIZE OF THE J-BOX SHOWN TO EXTEND FEEDERS TO |
| | NEW PANEL LOCATION. FBC 107.3.5 |
| | 6. PLEASE PROVIDE RECEPTACLES OUTLET FOR THE REQUIRED |
| | SHOW WINDOW RECEPTACLES PER NEC 210.62 AND CALCULATIONS |
| | PER NEC 220.43A |
| | 7. PLEASE ADDRESS BUILDING AND MECHANICAL COMMENTS |
| | RELATED TO ELECTRICAL. |
| | 8. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE |
| | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING |
| | THIS PROJECT. |
| | |
| | |