Plan Review Notes
Plan Review Notes For Permit 17010872
Permit Number 17010872
Review Stop E
Sequence Number 1
Notes
Date Text
2017-02-13 08:05:33INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL
 LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE
 ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, KITCHEN
 HOODS ETC. A NOTE WILL SUFFICE.
 2. ADD A GENERAL NOTE TO PROVIDE PER FBC EC 405.7.4-
 COMPLETION DOCUMENTS PER CODE SECTION. FBC EC 405.7.3-
 VOLTAGE DROP
 3. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE
 VERBIAGE IN CODE.
 4. PROVIDE A NOTE TO INDICATE COMPLIANCE WITH FBC EC
 405.2 AUTOMATIC LIGHTING CONTROL AND LIGHTING DENSITIES
 PER CODE SECTION.
 5. PROVIDE SIZE OF THE J-BOX SHOWN TO EXTEND FEEDERS TO
 NEW PANEL LOCATION. FBC 107.3.5
 6. PLEASE PROVIDE RECEPTACLES OUTLET FOR THE REQUIRED
 SHOW WINDOW RECEPTACLES PER NEC 210.62 AND CALCULATIONS
 PER NEC 220.43A
 7. PLEASE ADDRESS BUILDING AND MECHANICAL COMMENTS
 RELATED TO ELECTRICAL.
 8. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  