Plan Review Notes
Plan Review Notes For Permit 17010872
Permit Number 17010872
Review Stop B
Sequence Number 1
Notes
Date Text
2017-01-31 08:57:34BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17010872
 ADD: 120 S. OLIVE AVE. SUITE 102
 CONT: VILLA FRANCA DESIGN & DEVELOPMENT
 TEL: 561-575-2288
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 31/ 2017
 ACTION: DENIED
  
 1) SHEET A1:
 1A) SHEET A1 THE CORRIDORS THAT SURROUND THE TENANT
 SPACE ARE LABELED AS WALL TYPES WT1. SHEET A7 PROVIDES
 THE DETAIL OF WALL TYPE WT1 AND INDICATES THE ASSEMBLY
 FOR THE WALL IS TAKEN FROM THE 2014 FBC-B TABLE
 721.1.(1)(7). PLEASE NOTE THE HEADING FOR THIS WALL
 ASSEMBLY, STRUCTURE PARTS TO BE PROTECTED. APPLIES TO
 STEEL COLUMNS AND ALL PRIMARY TRUSSES.
 PLEASE LOOK AT THE TABLE 721.1(2) (13.1-13.3) THESE ARE
 WALL ASSEMBLIES FOR PARTITION WALLS NONCOMBUSTIBLE
 STUDS.
  
 2) SHEET A7 THERE ARE 2 DETAILS ST1 & WT3 WHICH
 REFERENCE THE 2014 FBC-B TABLE 722.2.1.4(2) TIME
 ASSIGNED TO FINISH MATERIALS ON THE EXPOSED SIDE OF THE
 WALL. PLEASE REVIEW SECTION 722.2.1.4 WALLS WITH GYPSUM
 WALLBOARD OR PLASTER FINISHES, CAST IN PLACE OR PRECAST
 CONCRETE WALLS WITH FINISHES OF GYPSUM WALLBOARD OR
 PLASTER APPLIED TO ONE OR BOTH SIDES SHALL BE PERMITTED
 TO BE CALCULATED IN ACCORDANCE WITH THE PROVISIONS OF
 THIS SECTION.
 FBC-B 713.2 CONSTRUCTION. SHAFT ENCLOSURES SHALL BE
 CONSTRUCTED AS FIRE BARRIERS IN ACCORDANCE WITH 707.
 FBC-B 707.3.1 SHAFT ENCLOSURES. THE FIRE RESISTANCE
 RATING OF THE FIRE BARRIER SEPARATING THE BUILDING AREA
 FROM THE SHAFT SHALL COMPLY WITH SECTION 713.4.
 FBC-B 713.4. FIRE RESISTANCE RATING. SHAFT ENCLOSURES
 SHALL HAVE A FIRE-RESISTANCE RATING NOT LESS THAN THE
 FLOOR ASSEMBLY PENETRATED, BUT NOT NEED EXCEED 2 HOURS.
 SHAFT ENCLOSURES SHALL MEET THE REQUIREMENTS OF
 703.2.1.
 FBC-B 703.2.1. NONSYMMETRICAL WALL CONSTRUCTION.
 INTERIOR WALLS AND PARTITIONS OF NONSYMMETRIC
 CONSTRUCTION SHALL BE TESTED WITH BOTH FACES EXPOSED TO
 THE FURNACE, AND THE SHORTEST DURATION OBTAINED FROM
 THE TWO TESTS CONDUCTED IN ACCORDANCE WITH ASTM E 119
 OR UL 263.
  
 3) SHEET A7 DETAIL WT3 SHOWS SHAFT CONSTRUCTION BUT
 DOES NOT PROVIDE THE PROTECTION FOR THE THROUGH FLOOR
 PENETRATION PER FBC-B 714.4 HORIZONTAL ASSEMBLIES.
 PENETRATIONS OF A FLOOR ASSEMBLY NOT REQUIRED TO BE
 ENCLOSED BY A SHAFT BY SECTION 712.1 SHALL BE PROTECTED
 IN ACCORDANCE WITH SECTION 714.4.1 THROUGH 714.4.2.2.
  
 4) SHEET A1 SHOWS A LUNCH COUNTER DOES SHOW 1
 ACCESSIBLE DINING AREA FACING THE KITCHEN MEETING THE
 0.05% ACCESSIBLE DINING SPACES. THE PLANS ALSO SHOW A
 COUNTER AT 42 INCHES AND 8 UNDER COUNTER BAR STOOLS.
 DISPERSION MAYBE AN ISSUE. A PATRON MAY FEEL THAT
 EQUIVALENCY(SECTION 103) HAS NOT BEEN REACHED SINCE THE
 ONLY ACCESSIBLE SEAT FACES THE KITCHEN. IF THERE WILL
 BE ADDITIONAL OUTSIDE SEASONAL SEATING THEN THE TOTAL
 NUMBER OF SEATS HAS TO BE RECALCULATED MEETING THE
 0.05% ACCESSIBLE DINING AND DISPERSION AS PER SECTION
 226.2 OF THE 2014 ACCESSIBILITY CODE.
  
 5) SHEET A1 SHOWS THE ENTRANCE INTO THE TENANT SPACE IS
 A UNKNOWN, THIS IS A ISSUE THAT NEEDS TO BE DETERMINED
 BEFORE PERMIT ISSUANCE. PLEASE SEE SECTION 202.4.1
 DISPROPORTIONATE COST 2014 ACCESS. CODE. A TENANT CAN
 BE MADE TO SPEND UP TO 20%($18,600.00) OF THE PERMIT
 VALUE $93,000.00 STATED IN THE VALUE OF THE PROJECT.
 THE 1ST ITEM ON THE LIST WHERE FUNDS HAVE TO BE SPENT
 IS AN ACCESSIBLE ENTRANCE.
  
 6) DISPROPORTIONATE COST 202.4.1 EITHER THE CONTRACTOR
 OR DESIGNER OF RECORD ON THEIR LETTER HEAD WILL NEED TO
 SHOW AN ITEMIZED LIST WHERE UP TO THE 20 % OF THE FUNDS
 $18,600.00 IN THE ORDER STATED IN THE CODE SECTION.
  
 7A) THE COVEERSHEET NEEDS TO LIST THE MINIMUM BUILDING
 TYPE FOR A 8 STORY BUILDING. 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1.1. COMMERCIAL BUILDINGS: BUILDING (3) TABLE
 503.
  
 7B) THE COVERSHEET INDICATES THIS IS A MERCANTILE
 OCCUPANCY, PLEASE NOTE THAT SMALL ASSEMBLY SPACES
 303.1.2(1) ROOMS USED FOR ASSEMBLY PURPOSES AND THE
 OCCUPANT LOAD IS LESS THAN 50 PERSONS THE OCCUPANCY
 WILL BE CLASSIFIED AS A B OCCUPANCY.
  
 7C) THIS IS A CHANGE OF OCCUPANCY AND NEED TO MEET ALL
 OF THE REQUIREMENTS OF 2014 EXISTING BUILDING CODE
 1001.3.1 PARTIAL CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE A PORTION OF AN EXISITNG BUILDING IS CHANGED TO A
 NEW OCCUPANCY CLASSIFICATION, SECTION 1012 (EXISTING
 BUILDING CODE) SHALL APPLY.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  