| Plan Review Notes For Permit 17010826 |
| Permit Number |
17010826 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-01-23 18:24:20 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SPECIFY THE MEAN ROOF HEIGHT AND ROOF SLOPE. FBC | | | 107.2.1 | | | | | | 2) SUBMIT SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | | ENHANCED FASTING OF THE BASE SHEET ON THE FLAT ROOF | | | AREAS. THE MAXIMUM DESIGN PRESSURE FOR THE SYSTEM THAT | | | WAS SELECTED (W-11) IS -52.5 PSF WHICH IS NOT ADEQUATE | | | FOR ROOF ZONES 2 AND 3. SEE NOTE 7 ON PAGE 2 OF THE | | | PRODUCT APPROVAL. | | | | | | | | | |
|