Plan Review Notes
Plan Review Notes For Permit 17010824
Permit Number 17010824
Review Stop B
Sequence Number 2
Notes
Date Text
2017-01-31 19:15:46PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 THE EMAIL THAT I RECEIVED FROM BILL MOORE WITH LEGACY
 CONTRACTING STATES THAT HIS CLIENT'S INSURANCE CARRIER
 IS REQUIRING HIM TO INSTALL A ROOF TO WALL CONNECTION
 THAT CONSISTS OF A STRAP THAT WRAPS OVER THE TRUSS IN
 ORDER TO RETAIN HIS HOMEOWNERS INSURANCE. HE STATED
 THAT THE HGA10KT ANGLE CONNECTOR WAS NOT ACCEPTABLE
 BECAUSE IT DOES NOT WRAP OVER THE TRUSS AND THAT THE
 LTT19 STRAP IS COST PROHIBITIVE. PER OUR TELEPHONE
 CONVERSATION, YOU DO NOT HAVE ACCESS TO THE FACE OF THE
 WALL ON EITHER SIDE TO ATTACH THE STRAPS WITHOUT HAVING
 TO REMOVE AND REPAIR THE WALL OR SOFFIT AND INCUR MORE
 COSTS. I HAVE DISCUSSED YOUR SITUATION WITH THE
 BUILDING OFFICIAL AND WE HAVE DETERMINED TWO OPTIONS
 WHICH YOU CAN USE TO ACCOMPLISH THE ROOF TO WALL
 CONNECTIONS IN ORDER TO SATISFY THE INSURANCE COMPANY'S
 REQUIREMENTS. THE FIRST IS TO USE A TESTED AND APPROVED
 STRAP IN ACCORDANCE WITH ITS PRODUCT APPROVAL. THE
 SECOND METHOD IS BY USING FBC 104.11 ALTERNATIVE
 MATERIALS, DESIGN AND METHODS OF CONSTRUCTION AND
 EQUIPMENT. AN ALTERNATIVE MATERIAL, DESIGN OR METHOD OF
 CONSTRUCTION SHALL BE APPROVED WHERE THE BUILDING
 OFFICIAL FINDS THAT THE PROPOSED DESIGN IS
 SATISFACTORY AND COMPLIES WITH THE INTENT OF THE
 PROVISIONS OF THIS CODE, AND THAT THE MATERIAL, METHOD
 OR WORK OFFERED IS, FOR THE PURPOSE INTENDED, AT LEAST
 THE EQUIVALENT OF THAT PRESCRIBED IN THIS CODE IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY. THE BUILDING OFFICIAL HAS
 REQUESTED THAT THE FLORIDA LICENSED ENGINEER PROVIDE A
 DETAIL AND CALCULATIONS SHOWING HOW THE STATED UPLIFT
 CAN BE RESISTED BY:
 -THE PULL OUT RESISTANCE OF THE 3/8" X 1-1/2" LAG
 SCREW.
 -THE ALLOWABLE BENDING STRESS OF THE 3/8" THICK SQUARE
 WASHER ACTING AS A CANTILEVER FROM THE BOLT TO THE
 POINT OF APPLICATION OF THE STRAP UPLIFT AT THE EDGE OF
 THE WASHER.
 -THE ALLOWABLE TENSILE STRENGTH OF THE STRAP AFTER
 DEDUCTING THE CROSS-SECTIONAL AREA OF STEEL REMOVED BY
 THE WHOLE DRILLED FOR THE 3/8" LAG BOLT.
 -THE SPECIFICATION OF THICKNESS, STEEL GRADE, AND
 ALLOWABLE BENDING STRESS OF THE WASHER AND STEEL GRADE
 AND ALLOWABLE TENSILE STRESS OF THE SIMPSON MSTA STRAP.
  
  