| 2017-01-25 07:39:23 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE INSTALLATION INSTRUCTION DRAWINGS FOR THE | | | DYNAMIC 5V CRIMP METAL ROOFING DOES NOT LIST A FLORIDA | | | PRODUCT APPROVAL NUMBER. PRINT OUT THE COVER SHEETS | | | WHICH HAVE THE FL NUMBER AND REFERENCES THESE | | | INSTALLATION DRAWINGS AND ATTACH THEM TO THE DRAWINGS. | | | FBC 107.2.1 | | | | | | 2) THIS PROJECT IS LOCATED WITHIN 600 FEET OF THE | | | INTRACOASTAL WATERWAY AND IS CLASSIFIED AS EXPOSURE | | | CATEGORY D. THE ENHANCED FASTENING CALCULATIONS THAT | | | WERE SUBMITTED ARE FOR EXPOSURE C. SUBMIT TWO SETS OF | | | CORRECTED CALULATIONS. FBC-R301.2.1.4.3 & R301.2.1 | | | | | | 3) THE ENHANCED FASTENING CALCULATIONS THAT WERE | | | SUBMITTED REFER TO FL 1654 - R17 AND THE EVALUATON | | | REPORT THAT WAS SUBMITTED IS FL1654 - R19. THE | | | INFORMATION DOES NOT MATCH BETWEEN THE TWO ITEMS THAT | | | WERE SUBMITTED. SUBMIT NEW FASTENING CALCULATIONS BASED | | | ON THE UP TO DATE REVISION R-19 VERSION OF FL 1654. | | | MAKE SURE THAT THE SYSTEM NUMBERS, DESIGN PRESSURES, | | | PAGE NUMBERS AND OTHER INFORMATION ON THE ENGINEERING | | | CORRESPONDS WITH THE PRODUCT APPROVAL. FBC - R301.2.1 | | | | | | 4) SEE HURRICANE MITIGATION COMMENTS ON PERMIT NUMBER | | | 17010824. |
|