2017-03-29 15:36:14****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PER BUILDING OFFICIAL, A DESIGN PROFESSIONAL
 LICENSED BY FS471 OR FS481 IS TO SPECIFY DESIGN
 PRESSURES. THE SEOR HAS A DISCLAIMER ON THE REVIEW
 STAMP AND IS NOT TAKING RESPONSIBILITY FOR THE DESIGN
 PRESSURES. SHEET 01 OF 11 PELLA SHOP DRAWINGS INCLUDES
 A STATEMENT THAT IT REQUIRES REVIEW BY A LOCAL
 ENGINEER. SHEET S-102 STATES THAT DESIGN PRESSURES CAN
 BE IN ACCORDANCE WITH FBC. FBC CHAPTER 16 INCLUDES A
 TABLE UP TO 60 FEET. THIS BUILDING IS OVER 60 FEET.
  
 2. PELLA SHOP DRAWINGS - MULLIONS ARE SHOWN. MULLIONS
 ARE REQUIRED TO HAVE ENGINEERING OR PRODUCT APPROVAL,
 FBC 1609. WERE DETAILS FOR THE MULLION INCLUDED IN THE
 MASTER PERMIT? ADVISE WHERE THIS INFORMATION CAN BE
 FOUND, OR SUBMIT AT THIS TIME.
  
 3. THE PRODUCT APPROVAL FOR THE FRENCH DOOR IS EXPIRED;
 GOVERNING CODE FOR THIS PROJECT IS FBC 2014, FS553.
  
 4. DESIGN PRESSURES REVIEWED ARE SUBJECT TO ENGINEERING
 NOT YET RECEIVED WHICH SPECIFY DESIGN PRESSURES FOR
 THIS COMMERCIAL THRESHOLD BUILDING.
  
 5. THIS REVISION WILL BE ISSUED WITH PROVISO;
 INSTALLATION IS TO BE IN CONFORMANCE WITH THE ISSUED
 PERMIT. ALL DOORS IN THE MEANS OF EGRESS FOR ASSEMBLY
 OCCUPANCY TO INCLUDE PANIC BARS OR FIRE EXIT HARDWARE
 FBC B 1008.
  
 6. PLANS ARE DIFFICULT TO READ AND WILL NOT BE LEGIBLE
 AFTER SCANNING DUE TO SIZE OF TEXT, FBC 107; PROVIDE
 FULL SIZE LEGIBLE PLANS.
  
  