2017-01-26 15:24:05****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REFER TO BULLETIN #5, REVISED PAGE S102. DESIGN
 PRESSURES FOR ZONE 4 IS +-48PSF, ZONE 5 +48.6 / -88.8
 REGARDLESS OF SIZE OF OPENING. REVISE SHEET 1 OF 11
 ACCORDINGLY.
  
 2. FS 553, FLORIDA STATE OR LOCAL PRODUCT APPROVAL IS
 REQUIRED. CUT SHEETS OF COPIED ENGINEERING WHICH MAY BE
 FROM A PRODUCT APPROVAL WERE SUBMITTED. THE CUT SHEETS
 LACK A PRODUCT APPROVAL NUMBER.
  
 IF A LOCAL PRODUCT APPROVAL IS REQUIRED, SEE
 REQUIREMENTS IN FLORIDA STATUTE, PROVIDE ORIGINAL
 ENGINEERING, EVALUATION REPORT, ETC. DOCUMENTS PREPARED
 BY AN ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO
 BE SIGNED, SEALED, DATED ORIGINALS. (PRODUCT APPROVALS
 FOR WHICH THE ORIGINAL IS ON FILE WITH THE STATE ARE
 EXEMPTED FROM THIS STATUTE.)
  
 3. A NOTE ON THE PLANS STATE THAT OPERABLE DOORS ARE TO
 BE INSTALLED IN ZONE 4 ONLY. PLEASE ADVISE AS TO WHICH
 FIXED DOORS ARE PROPOSED IN ZONE 5.
  
 THE FIXED PANEL HAS A DESIGN PRESSURE LIMITATION OF +70
 / -85 PSF, WHICH DOES NOT MEET THE ENGINEER OF RECORD'S
 DESIGN PRESSURE REQUIREMENT FOR ZONE 5. DESIGN
 PRESSURES FOR PRODUCTS INSTALLED IN BOTH ZONES
 (PARTIALLY IN ZONE 4, PARTIALLY IN ZONE 5) MAY, TO THE
 BEST OF MY KNOWLEDGE, BE INTERPOLATED (PLEASE CONSULT
 WITH EOR).
  
 4. THE INSWING DOOR SHOWN ON SHEET 1 (1ST FLOOR H
 INSWING) APPEARS TO HAVE A DESIGN PRESSURE LIMITATION
 OF +40 / -50. IT IS POSSIBLE THAT OTHER DOORS DO NOT
 COMPLY WITH THE ENGINEER OF RECORD'S SPECIFIED DESIGN
 PRESSURES. A COMPLETE REVIEW WAS NOT DONE. IT IS
 SUGGESTED THAT A SCHEDULE SHOWING THE DP LIMIT FOR EACH
 PRODUCT BE CREATED SO COMPLIANCE CAN QUICKLY BE
 VERIFIED.
  
 5. DESIGN PROFESSIONAL IS TO VERIFY THAT ALL PRODUCTS
 APPROVED FOR USE COMPLY WITH THE DESIGN PRESSURES FOR
 THE PROJECT PRIOR TO SUBMITTAL, FBC 107.
  
  
  
  