| 2017-01-24 08:30:07 | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE SYSTEM TYPE E(6) ON PAGE 26 OF THE PRODUCT | | | APPROVAL HAS A MAXIMUM DESIGN PRESSURE OF -60 PSF AND | | | REQUIRES ENHANCED FASTENING. SUBMIT SIGNED AND SEALED | | | RAS 117 CALCULATIONS FOR ENHANCED FASTENING OF THE BASE | | | SHEET IN THE PERIMETER AND CORNER AREAS AS REQUIRED BY | | | LIMITATION #7 ON PAGE 42 OF THE CERTAINTEED MODIFIED | | | BITUMEN ROOFING SYSTEM ( NOA NO. 14-0529.02 ). |
|