| 2017-01-26 06:48:19 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. PLEASE PROVIDE A ONE-LINE DIAGRAM REFLECTING ALL | | | PANELBOARDS, CORD CONDUCTOR SIZE ARRANGEMENT. FBC | | | 107.3.5 MINIMUM PLAN REVIEW CRITERIA. | | | 2. PROVIDE A PANEL SCHEDULE REFLECTING ALL ELECTRICAL | | | LOADS; EXAMPLE LIGHTING, RECEPTACLES AND MECHANICAL | | | EQUIPMENT. LOAD CALCULATIONS REQUIRED TO BE WITHIN | | | GENERATOR CAPACITY. FBC 107.3.5 MINIMUM PLAN REVIEW | | | CRITERIA. | | | 3. SHOW BONDING AND GROUNDING SCHEME FOR THE GENERATOR | | | AND ANY CONDUCTIVE METAL PARTS OF THE TENT. FOLLOW NEC | | | 250 REQUIREMENTS. | | | 4. PROVIDE A FIXTURE SCHEDULE AND PRODUCT DATA SHEETS | | | REFLECTING ALL LIGHTING FIXTURES BEING USED. LISTINGS | | | WILL BE VERIFIED. FBC 107.3.5 MINIMUM PLAN REVIEW | | | CRITERIA. | | | 5. PROVIDE GENERAL NOTES TO COMPLY WITH ALL APPLICABLE | | | TEMPORARY REQUIREMENTS PER NEC 590, REGARDING GFCI | | | PROTECTION, PROTECTION AGAINST ACCIDENTAL DAMAGE | | | (CORDS), LAMP PROTECTION, SUPPORTS ETC. | | | 6. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE | | | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING | | | THIS PROJECT. | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|