2017-01-26 06:48:19INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PLEASE PROVIDE A ONE-LINE DIAGRAM REFLECTING ALL
 PANELBOARDS, CORD CONDUCTOR SIZE ARRANGEMENT. FBC
 107.3.5 MINIMUM PLAN REVIEW CRITERIA.
 2. PROVIDE A PANEL SCHEDULE REFLECTING ALL ELECTRICAL
 LOADS; EXAMPLE LIGHTING, RECEPTACLES AND MECHANICAL
 EQUIPMENT. LOAD CALCULATIONS REQUIRED TO BE WITHIN
 GENERATOR CAPACITY. FBC 107.3.5 MINIMUM PLAN REVIEW
 CRITERIA.
 3. SHOW BONDING AND GROUNDING SCHEME FOR THE GENERATOR
 AND ANY CONDUCTIVE METAL PARTS OF THE TENT. FOLLOW NEC
 250 REQUIREMENTS.
 4. PROVIDE A FIXTURE SCHEDULE AND PRODUCT DATA SHEETS
 REFLECTING ALL LIGHTING FIXTURES BEING USED. LISTINGS
 WILL BE VERIFIED. FBC 107.3.5 MINIMUM PLAN REVIEW
 CRITERIA.
 5. PROVIDE GENERAL NOTES TO COMPLY WITH ALL APPLICABLE
 TEMPORARY REQUIREMENTS PER NEC 590, REGARDING GFCI
 PROTECTION, PROTECTION AGAINST ACCIDENTAL DAMAGE
 (CORDS), LAMP PROTECTION, SUPPORTS ETC.
 6. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  