| Plan Review Notes For Permit 17010802 |
| Permit Number |
17010802 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-01-31 08:21:10 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17010802 | | | 1/31/17 | | | | | | 1) PROVIDE O/A CALCULATIONS FOR THE STORAGE ROOM. | | | | | | 2) CLARIFY THE PURPOSE OF EF-2 IN THE STORAGE ROOM AND | | | PROVIDE AN EXHAUST VENTILATION CALCULATION. PLEASE NOTE | | | AN INDEPENDENT EXHAUST SYSTEM MAY BE REQUIRED PER | | | COMMENT #3 BELOW. | | | | | | 3) CLARIFY WHAT MATERIALS OR CHEMICALS WILL BE STORED | | | IN THE STORAGE ROOM. REFER TO SECTION 414.1.3 FBC-14 | | | BUILDING AND, IF APPLICABLE, PROVIDE A REPORT | | | IDENTIFYING THE MAXIMUM EXPECTED QUANTITIES OF | | | HAZARDOUS MATERIALS TO BE STORED, USED IN A CLOSED | | | AND/OR OPEN SYSTEM AND SUBDIVIED TO SEAPARATELY ADDRESS | | | HAZARDOUS MATERIALS CLASSIFICATION CATEGORIES BASED ON | | | TABLE 307.1(1) AND 307.1(2). | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|