| Plan Review Notes For Permit 17010802 |
| Permit Number |
17010802 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-02-01 10:54:24 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE | | | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE | | | PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL | | | LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE | | | ALARM, ACCESS CONTROLS CARD READERS, PHONE AND DATA, | | | WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE. | | | 2. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3, | | | 405.7.4 SEE VERBIAGE IN THE CODE REGARDING VOLTAGE DROP | | | AND COMPLETIONS DOCUMENTS. | | | 3. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO | | | INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC | | | 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS FOR | | | MODIFICATIONS; SEE VERBIAGE IN CODE. | | | 4. FUTURE GENERATOR NOT PART OF SCOPE. CLARIFICATION | | | REQUIRED | | | 5. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE | | | TO CONTACT ME SHOULD YOU HAVE ANY | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|