| Plan Review Notes For Permit 17010799 |
| Permit Number |
17010799 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-05-03 11:44:29 | 539 OGSTON STREET | | | PERMIT #17010799 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | NEW COMMENT: FIRE PROTECTION DRAWING WAS NOT SUBMITTED | | | FOR REVIEW. | | | | | | ORIGINAL COMMENT: FOR ISSUANCE OF A GENERAL BUILDING | | | PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING | | | CODE REQUIRES SEALED FIRE PROTECTION CONSTRUCTION | | | DOCUMENTS FOR THE DESIGN OR ALTERATION OF 50 OR MORE | | | AUTOMATIC FIRE SPRINKLERS.PER FLORIDA ADMINISTRATIVE | | | CODE SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING | | | DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE | | | WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS | | | APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD | | | OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM | | | TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP | | | DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED | | | INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | |
|