| 2017-05-05 15:41:46 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17010799 |
| | ADD: 539 OGSTON ST. |
| | CONT: CANO INC. |
| | TEL: |
| | E-MAIL: |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: FRI. MAY 05/ 2017 |
| | ACTION: DENIED |
| | |
| | 1A) SEMI- COMPLIED. THE COVERSHEET STILL INDICATES |
| | BUILDINGS 1 & 3. THE 4300 MILLER PROPERTY WAS |
| | SUPPOSEDLY DELETED FROM THIS PORTION OF THE PROJECT ON |
| | THE VARIOUS ARCHITECTURAL SHEETS BUILDING 3 IS X-ED |
| | THROUGH. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 1B) COMPLIED. THE 4300 MILLER PROPERTY DELETED FROM |
| | THIS PORTION OF THE PROJECT. NOTE TO HAVE 2 DIFFERENT |
| | OWNERS INVOLVED IN THE PROJECT THE DOCUMENT UNITY OF |
| | CONTROL WILL HAVE TO BE DEVELOPED BY THE CITY LAWYERS. |
| | |
| | 1C) COMPLIED. 308.4 INSTITUTIONAL GROUP I-2. BUILDINGS |
| | AND STRUCTURES USED FOR MEDICAL CARE ON A 24-HOUR BASIS |
| | FOR MORE THAN FIVE PERSONS WHO ARE INCAPABLE OF |
| | SELF-PRESERVATION. THIS GROUP SHALL INCLUDE, BUT NOT BE |
| | LIMITED TO, THE FOLLOWING: DETOXIFICATION FACILITIES. |
| | ZONING REQUIREMENT: APPLIED FOR A CLASS B USE. |
| | |
| | 1D)COMPLIED. THE OCCUPANCY I-2 BUILDING TYPE VA. |
| | |
| | 2) SHEET A-101: |
| | 2A) COMPLIED. BUILDING 1- BUILDING CATEGORY II/ 170 |
| | MPH/ 3 SECOND GUST/ VULT WIND DESIGN. |
| | |
| | 2B) 2ND REQUEST. SHEET A-101 SHOWS THAT BOTH TYPES OF |
| | FIRE SPRINKLERS NFPA 13 (903.3.1.1) AND NFPA 13R |
| | (903.3.1.2). WITH THE BUILDING 3 ELIMINATED FROM THIS |
| | PORTION OF THE PROJECT, IT IS ASSUMED THE NFPA 13R |
| | (903.3.1.2) WILL BE INSTALLED IN THE GROUP I-2 |
| | OCCUPANCY. THIS IS ALLOWED BY 903.2.6 BUT IN DOING SO |
| | YOU CANNOT TAKE THE 25% FOR FIRE SPRINKLERS SEE TABLE |
| | FBC-B 705.8 FOOTNOTE FOR S (SPRINKLERS) SPRINKLERS HAVE |
| | TO COMPLY WITH 903.3.1.1 OR NFPA 13. PLEASE REFIGURE |
| | BOTH THE HEIGHT OF WALLS FROM 18 FEET IN HEIGHT AND |
| | WINDOW AND DOOR OPENINGS AT 10 % IF 13R SPRINKLERS ARE |
| | TO BE INSTALLED. CLARIFY ALSO ON SHEET A-101. |
| | 1ST ROUND OF COMMENTS. BUILDING # 1 SHOWS WINDOWS ON |
| | THE NORTH/ SOUTH WALLS, THE WALLS ARE INDICATED ON |
| | SHEET A1-101 TO BE EITHER 5-0 FEET AWAY FROM THE |
| | PROPERTY LINE OR 5.5 FEET AWAY FROM THE PROPERTY LINE. |
| | PLEASE PROVIDE THE TOTAL AMOUNT OF SQUARE FEET OF |
| | WINDOWS AND DOORS AND THE PERCENTAGE OF OPENINGS WITH |
| | IN THE WALL. AND COMPLIANCE WITH FBC-B TABLE 705.8. |
| | PLEASE ALSO PROVIDE THE AMOUNT OF OPENINGS AND |
| | PERCENTAGE OF WALL WITHIN THE EAST WALL AS WELL. PLEASE |
| | NOTE THE ALLOWABLE AREA FOR FIRE SPRINKLERS CANNOT BE |
| | TAKEN SENSE THE SPRINKLERS INSTALLED ARE A NFPA 13R. |
| | |
| | 2C-G) COMPLIED |
| | |
| | 3-5) COMPLIED. |
| | |
| | 6) BUILDING # 1. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 7) FIRE SPRINKLER PLANS REQUIRED. W. P. B. |
| | ADMINISTRATIVE CODE105.3.1.2(2) FIRE SPRINKLER |
| | DOCUMENTS FOR ANY NEW BUILDING OR ADDITION WHICH |
| | INCLUDES A FIRE SPRINKLER SYSTEM WHICH CONTAINS 50 OR |
| | MORE SPRINKLER HEADS. A CONTRACTOR I, CONTRACTOR II OR |
| | CONTRACTOR IV, CERTIFIED UNDER SECTION 633.521, FLORIDA |
| | STATUTES, MAY DESIGN A FIRE SPRINKLER SYSTEM OF 49 OR |
| | FEWER HEADS AND MAY DESIGN THE ALTERATION OF AN |
| | EXISTING FIRE SPRINKLER SYSTEM IF THE ALTERATION |
| | CONSISTS OF THE RELOCATION, ADDITION OR DELETION OF NOT |
| | MORE THAN 49 HEADS, NOT WITHSTANDING THE SIZE OF THE |
| | EXISTING FIRE SPRINKLER SYSTEM. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |