| 2017-02-07 16:42:04 | 1ST REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | CODE REQUIREMENTS; |
| | FLORIDA BUILDING CODE ACCESSIBILITY 2014 5TH EDITION |
| | FLORIDA BUILDING CODE PLUMBING 2014 5TH EDITION |
| | |
| | 1. PER THE FLORIDA BUILDING CODE ACCESSIBILITY SEC |
| | 223.2.1 AT LEAST ONE OF THE PATIENT ROOMS SHALL COMPLY |
| | WITH FBC ACC 805 |
| | |
| | 2. PER FBC ACC 805.4 THE BATHROOM SHALL COMPLY WITH FBC |
| | ACC 603 THROUGH 610 |
| | |
| | 3. PER FBC ACC 213.2 + 213.3.2 ONE BATHROOM PER SEX FOR |
| | THE STAFF SHALL COMPLETE WITH FBC ACC 603+604 |
| | |
| | 4. THE SINK IN THE BREAKROOM SHALL COMPLY WITH FBC ACC |
| | 606 |
| | |
| | 5. WILL THE LAUNDRY BE USED EXCLUSIVELY BY THE STAFF IF |
| | IT IS USED BY PATIENTS OR FAMILY IT SHALL COMPLY WITH |
| | FBC ACC 611 |
| | |
| | 6.SHT. P-1 + P-5 THE NOTE ON THE GAS SERVICE READS CW |
| | SERVICE 18 FU PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 7. THE HOT WATER SYSTEM IN BUILDING 1 SHALL HAVE A |
| | RECIRCULATING SYSTEM PER FBC PL 607.2 HOT OR TEMPERED |
| | WATER SUPPLY TO FIXTURES. |
| | THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING, |
| | FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT |
| | REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET |
| | (15 240 MM). RECIRCULATING SYSTEM PIPING AND |
| | HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF |
| | HOT OR TEMPERED WATER. |
| | |
| | 8. A BACKFLOW IS REQUIRED ON THE ICE MACHINE. PER FBC |
| | PL 608.3 |
| | |
| | 9. THE LAVATORY'S IN THE BATHROOMS USED BY VISITORS |
| | SHALL HAVE TEMPERED WATER PER FBC PL 416.5 TEMPERED |
| | WATER FOR PUBLIC HAND-WASHING FACILITIES. |
| | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| | WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3. |
| | |
| | 10. PLEASE PROVIDE MANUFACTURE SPECS FOR THE LENT TRAP. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND |
| | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON |
| | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| | |