| 2017-01-30 16:14:00 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17010799 |
| | 1/30/17 |
| | |
| | 1) THE ENERGYGAUGE COMPLIANCE SUBMITTALS FOR BUILDINGS |
| | 1 & 3 MUST BE SIGNED AND DATED BY THE OWNER/AGENT- SEE |
| | PAGE 3 OF THE DOCUMENTS. |
| | |
| | 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| | SPLIT AND ROOFTOP SYSTEMS. |
| | |
| | 3) THE O/A CALCULATIONS ARE INCORRECT FOR THE PATIENT |
| | ROOMS. REFER TO TABLE 403.3: 25 CFM PER PERSON |
| | REQUIRED. |
| | |
| | 4) PROVIDE A DETAIL FOR INSTALLATION OF THE CEILING |
| | DAMPERS IN THE BLDG. #1 CORRIDORS. |
| | |
| | 5) A DUCT SMOKE DETECTOR IS REQUIRED IN THE RETURN AIR |
| | SYSTEM OF RTU-1 UNLESS IT CAN BE VERIFIED BY |
| | MANUFACTURER'S SPECIFICATIONS THAT THE SYSTEM CANNOT |
| | EXCEED 2000 CFMS OF SUPPLY AIR. |
| | |
| | 6) SUBMIT SPECS FOR THE WASHER/DRYER UNITS WITH DRYER |
| | VENTING INSTRUCTIONS FOR MULTIPLE UNITS. |
| | |
| | 7) PROVIDE STRUCTURAL ENGINEERING FOR: A) INSTALLATION |
| | OF THE RTU INCLUDING THE ROOF OPENING AND |
| | REINFORCEMENT, AND THE CURB AND RTU ATTACHMENTS. B) |
| | INSTALLATION OF THE CU WALL BRACKETS- SECTION 301.15. |
| | |
| | 8) REFER TO SECTION 401.4 AND PROVIDE CLEARANCE |
| | DISTANCE MEASUREMENTS FOR THE O/A INTAKE OPENING FOR |
| | AHU-3. |
| | |
| | 9) BASED ON THE STRUCTURAL COMMENTS THE OCCUPANCY |
| | CLASSSIFICATION OF THE BUILDING MAY BE IN QUESTION. |
| | PLEASE NOTE THAT ADDITIONAL REVIEW COMMENTS MAY OCCUR |
| | AFTER THIS ISSUE IS RESOLVED AND CORRECTED PLANS ARE |
| | RESUBMITTED. |
| | |