| 2017-06-30 13:35:42 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE SURVEY THAT WAS SUBMITTED SHOWS THAT THE |
| | EXISTING STRUCTURE IS 9.6 FEET FROM THE SIDE PROPERTY |
| | LINES. THE PLANS SPECIFY A 5 FEET ADDITION TO THE WEST |
| | SIDE OF THE EXISTING STRUCTURE. THIS WILL LEAVE A |
| | DISTANCE OF 4.6 FEET TO THE PROPERTY LINE. THE SITE |
| | PLAN ON SHEET A-1 SHOWS 5 FEET TO THE PROPERTY LINE. |
| | PLEASE CORRECT. FBC 107.2.1 NOTE: THE ADDITIONAL BLOCK |
| | WALL THAT IS SHOWN ON THE PLANS BESIDE THE EXISTING |
| | EXTERIOR BLOCK WALL COULD BE ELIMINATED IN ORDER TO |
| | PROVIDE AN ADDITIONAL 8" OF INTERIOR SPACE TO THE |
| | PROPOSED ADDITION. |
| | |
| | 2) THE REVISED PLANS SPECIFY A 4040 HR EGRESS WINDOW IN |
| | THE EXISTING BEDROOM. THE SOUTH ELEVATION ON SHEET A-2 |
| | SHOWS A SINGLE HUNG WIND. PLEASE CLARIFY. IF THIS IS A |
| | NEW WINDOW IN THE EXISTING OPENING SUBMIT 2 SETS OF |
| | PRODUCT APPROVALS FOR THE HORIZONTAL SLIDING WINDOW. IF |
| | IT IS EXISTING, SPECIFY AS SUCH ON THE PLANS. FBC |
| | 107.2.1 |
| | |
| | 3) FBC ENERGY CONSERVATION SECTIONS R101.5.1.1.1 OR |
| | R101.5.1.1.2. SUBMIT TWO SETS OF ENERGY COMPLIANCE |
| | FORMS AS REQUIRED. |
| | |
| | 4) PROVIDE THE FL# FOR THE JELD-WEN OPAQUE WOOD EDGE |
| | STEEL EXTERIOR DOORS. THE DOCUMENTS THAT WERE SUBMITTED |
| | DO NOT SPECIFY THE FL NUMBER. |
| | |
| | 5) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD, |
| | CHARLES C. MITCHELL, P.E. FBC 107.3.4 |
| | |
| | 6) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A |
| | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |
| | |