| 2017-01-27 07:54:32 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) A FLORIDA CGC LICENSE DOES NOT ALLOW THE CONTRACTOR | | | TO DO RE-ROOFING WORK. PROVIDE A FLORIDA CCC LICENSE OR | | | A PALM BEACH COUNTY LICENSE THAT ALLOWS YOU TO DO A | | | RE-ROOF. FLORIDA STATUTES 489 | | | | | | 2) THE SYSTEM THAT WAS SELECTED ON PAGE 27 OF NOA NO. | | | 14-0529.02 HAS A MAXIMUM DESIGN PRESSURE OF -60 PSF AND | | | WILL REQUIRE INCREASED FASTENER DENSITIES. SUBMIT TWO | | | SETS OF SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | | ENHANCED FASTENING IN THE PERIMETER AND CORNER AREAS, | | | AS REQUIRED BY GENERAL LIMITATION NUMBER 7 ON PAGE 42 | | | OF NOA NO. 14-0529.02. | | | |
|