2017-01-27 07:54:32PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) A FLORIDA CGC LICENSE DOES NOT ALLOW THE CONTRACTOR
 TO DO RE-ROOFING WORK. PROVIDE A FLORIDA CCC LICENSE OR
 A PALM BEACH COUNTY LICENSE THAT ALLOWS YOU TO DO A
 RE-ROOF. FLORIDA STATUTES 489
  
 2) THE SYSTEM THAT WAS SELECTED ON PAGE 27 OF NOA NO.
 14-0529.02 HAS A MAXIMUM DESIGN PRESSURE OF -60 PSF AND
 WILL REQUIRE INCREASED FASTENER DENSITIES. SUBMIT TWO
 SETS OF SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 ENHANCED FASTENING IN THE PERIMETER AND CORNER AREAS,
 AS REQUIRED BY GENERAL LIMITATION NUMBER 7 ON PAGE 42
 OF NOA NO. 14-0529.02.
  