| Date |
Text |
| 2017-02-17 11:05:42 | 1ST REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1.PER FBC PL 403.2 SEPARATE FACILITIES ARE REQUIRED FOR |
| | BOTH SEX SO BOTH BATHROOMS SHALL BE ACCESSIBLE. PER FBC |
| | ACC 213.2 TOILET ROOMS AND BATHING ROOMS. |
| | WHERE TOILET ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL |
| | COMPLY WITH 603 |
| | |
| | 2. THE ADA BATHROOM LAYOUT ON THE MEP PAGES DOES NOT |
| | MATCH SHT A1.0 PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 3. SHT. P-3 THE GREASE WASTE RISER THE HORIZONTAL VENT |
| | FOR P-7 IS NOT ALLOWED IT SHALL CONNECT ABOVE THE |
| | CENTERLINE OF THE HORIZONTAL DRAIN PIPE. PER FBC PL |
| | 905.3 |
| | |
| | 4. SHOW TRAPS ON RISER DIAGRAM FOR P-7, FS-1, FD-1. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 5. TRAP PRIMERS ARE REQUIRED ON ALL FLOOR DRAINS. PER |
| | FBC PL 1002.4 |
| | |
| | 6. IF YOUR USING A GARBAGE DISPOSAL ON P-4 IT SHALL |
| | COMPLY WITH FBC PL 1003.3.2 FOOD WASTE GRINDERS. |
| | WHERE FOOD WASTE GRINDERS CONNECT TO GREASE |
| | INTERCEPTORS, A SOLIDS INTERCEPTOR SHALL SEPARATE THE |
| | DISCHARGE BEFORE CONNECTING TO THE GREASE INTERCEPTOR. |
| | SOLIDS INTERCEPTORS AND GREASE INTERCEPTORS SHALL BE |
| | SIZED AND RATED FOR THE DISCHARGE OF THE FOOD WASTE |
| | GRINDER. EMULSIFIERS, CHEMICALS, ENZYMES AND BACTERIA |
| | SHALL NOT DISCHARGE INTO THE FOOD WASTE GRINDER. |
| | |
| | 7. DRAIN FOR THREE COMP SINK NOT SHOWN ON RISER PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 8. EXISTING HAND SINK NEXT6T TO MOP SINK IS NOT SHOWN |
| | ON RISER PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 9. PROVIDE THE SIZE AND SIZING CALCULATIONS FOR |
| | EXISTING GREASE TRAP. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 10. THE EXISTING GREASE TRAP SHALL BE INSPECTED AND |
| | VERIFIED TO BE STRUCTURALLY SOUND AND IN GOOD WORKING |
| | ORDER BY A SIGNED AND SEALED LETTER FROM THE ENGINEER. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND |
| | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON |
| | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| | |