| 2017-02-03 17:33:02 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A1.1 - A WOOD FENCE IS INDICATED AT THE EXIT |
| | PATH LEADING FROM THE EXIT STAIR DOOR AND HALLWAY EXIT |
| | DOOR. |
| | |
| | PER NFPA 101, CHAPTER 7 MEANS OF EGRESS |
| | |
| | 7.2.2.5.2* EXPOSURES. |
| | 7.2.2.5.2.1 WHERE NONRATED WALLS OR UNPROTECTED OPENING |
| | ENCLOSE THE EXTERIOR OF A STAIRWAY, OTHER THAN AN |
| | EXISTING STAIRWAY, AND THE WALLS OR OPENINGS ARE |
| | EXPOSED BY OTHER PARTS OF THE BUILDING AT AN ANGLE OF |
| | LESS THAN 180 DEGREES, THE BUILDING ENCLOSURE WALLS |
| | WITHIN 10 FT (3050 MM) HORIZONTALLY OF THE NONRATED |
| | WALL OR UNPROTECTED OPENING SHALL BE CONSTRUCTED AS |
| | REQUIRED FOR STAIRWAY ENCLOSURES, INCLUDING OPENING |
| | PROTECTIVES. |
| | |
| | |
| | THE NON RATED FENCE IS NOT IN COMPLIANCE WITH THE |
| | ABOVE, PLEASE CORRECT. |
| | |
| | |
| | |
| | 2) SHEET A1.1 - A CONCRETE WALL IS INDICATED NEXT TO |
| | THE EXISTING BACKFLOW PREVENTOR. THERE IS NO SEPARATION |
| | DIMENSION INDICATED AND OR ANY INDICATION THAT THIS |
| | WALL WILL NOT INTERFERE WITH ANY REPAIR/TESTING AND/OR |
| | MAINTENANCE WORK. |
| | |
| | PER NFPA 24, UNDERGROUND FIRE LINE |
| | |
| | 6.5 BACKFLOW PREVENTION ASSEMBLIES |
| | 6.5.1 WHERE USED IN ACCORDANCE WITH 6.2.11(4), BACKFLOW |
| | PREVENTION ASSEMBLIES SHALL BE INSTALLED IN ACCORDANCE |
| | WITH THEIR INSTALLATION INSTRUCTIONS. |
| | |
| | NFPA 13 |
| | |
| | 8.17.4.6* BACKFLOW DEVICES. |
| | |
| | A.8.17.4.6 WHERE BACKFLOW PREVENTION DEVICES ARE |
| | INSTALLED, THEY SHOULD BE IN AN ACCESSIBLE LOCATION TO |
| | PROVIDE FOR SERVICE AND MAINTENANCE. |
| | |
| | PLEASE PROVIDE A SPECIFIC SEPARATION DIMENSION AND A |
| | REVIEW/NARRATIVE FROM THE FIRE SPRINKLER |
| | INSTALLER/MAINTENANCE CONTRACTOR THAT IT COMPLIES WITH |
| | THEIR REQUIRMENTS AND/OR THE CODE. |
| | |
| | |
| | |
| | 3) SHEET A1.1 - THERE IA A CONCRETE WALL/STRUCTUREL BY |
| | THE BACKFLOW PREVENTOR THAT MAY CROSS OVER THE |
| | UNDERGROUND FIRE LINE. |
| | |
| | PER NFPA 24, UNDERGROUND FIRE LINE |
| | |
| | 10.6 PROTECTION AGAINST DAMAGE. |
| | 10.6.1 PIPE SHALL NOT BE RUN UNDER BUILDINGS. |
| | |
| | 10.6.5* PIPE JOINTS SHALL NOT BE LOCATED UNDER |
| | FOUNDATION FOOTINGS. |
| | |
| | |
| | PLEASE PROVIDE A DETAILED REVIEW FROM A CERTIFIED |
| | ENGINEER OR OTHER QUALIFIED ENTITY REGARDING THE ABOVE |
| | NOTE AND THAT THE WALL WILL NOT INTERFERE WITH ANY |
| | POSSIBLE CONDITION OR MAINTENANCE/REPAIR CONCERNS. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |