| 2017-02-23 15:16:55 | 1ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL |
| | 1ST REVIEW FBC 2014 EXISTING BUILDING |
| | ALTERATION LEVEL II |
| | |
| | 1) YOU SHOULD ADD NOTES TO THE PLAN TO INDICATE THE |
| | CODE IN EFFECT AND THE LEVEL OF ALTERATION AS FOLLOWS: |
| | |
| | FBC 2014 5TH ED. RESIDENTIAL |
| | FBC 2014 EXISTING BUILDING |
| | ALTERATION LEVEL II |
| | |
| | 2) PROVIDE AND ENERGY SUBMITTAL PER FBC 107. |
| | |
| | 3) THE DESIGNER OF RECORD IN REQUIRED TO PRINT HIS/HER |
| | NAME UPON PLAN AND SIGN THE PLAN. FBC-107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. ALL INFORMATION, |
| | DRAWINGS, SPECIFICATIONS AND ACCOMPANYING DATA SHALL |
| | BEAR THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE |
| | FOR THE DESIGN. |
| | |
| | 4) THE SHUTTER PRODUCT DOES NOT SHOW EVIDENCE OF REVIEW |
| | AND APPROVAL FOR USE BY THE DESIGNER OF RECORD. THIS |
| | MAY BE RESOLVED BY PROVIDING A SHUTTER INSTALLATION |
| | SCHEDULE LISTING THE PRODUCT APPROVAL NUMBER IN THE |
| | SCHEDULE AS HAS BEEN DONE WITH THE WINDOWS AND DOORS |
| | AND ALSO INCORPORATINNG AN ANCHOR SCHEDULE FOR THE |
| | SHUTTER TRACKS SPECIFYING THE STRUCTURE TYPE, ANCHOR |
| | TYPE, AND ANCHOR SPACING CONSISTENT WITH THE PRODUCT |
| | INFORMATION. FBC 107.3.4 - PROVIDE PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD. SPECIFICALLY, PROVIDE SHUTTER SUBMITTAL. |
| | |
| | 5) PROVIDE DETAILS TO SHOW EXISTING WALL AND CEILING |
| | INSULATION AND PROPOSED WALL AND CEILING INSULATION. |
| | |
| | |