| 2017-01-20 09:25:23 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17010634 |
| | W. P. B. MASTER: 16080300 |
| | ADD: 5016 S. DIXIE HWY. |
| | CONT: THERMA SEAL ROOF SYSTEMS LLC |
| | TEL: 561-223-2096 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JAN. 20/2017 |
| | ACTION: DENIED |
| | |
| | 1) THE DESIGNER OF RECORD HAS NOT REVIEWED THE ROOFING |
| | PRODUCT APPROVAL NOR APPLIED THEIR SHOP DRAWING STAMP |
| | OF APPROVAL. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 2) THE CONTRACTOR OF RECORD FAILED TO PRODUCE THE |
| | NECESSARY SHEETS OF THE PRODUCT APPROVAL NECESSARY FOR |
| | A THOROUGH REVIEW. MISSING SHEETS FROM ROOFING APPROVAL |
| | FL16440-R9 APPENDIX SHEETS 2-3. ADDITIONAL INFORMATION |
| | REQUIRED. 107.2.1.3, MISSING DOCUMENTS. |
| | |
| | 3) THE SUB-SYSTEMS FROM APPENDIX 1, PAGES 45 OF 46 |
| | SYSTEM NUMBER R-53 IS CIRCLED. EXISTING ROOF SYSTEM |
| | WITH GRANULE-SURFACED MODIFIED BITUMEN CAP SHEET |
| | INSTALLED OVER TECTUM ROOF DECK. APPENDIX SHEETS 2-3 |
| | USE AND LIMITATION OF THE VARIOUS SUB-SYSTEMS NOTE |
| | NUMBER 12 THE EXISTING ROOF SYSTEM SHALL BE CAPABLE OF |
| | RESISTING PROJECT DESIGN PRESSURES ON ITS OWN MERIT TO |
| | THE SATISFACTION OF THE AHJ, AS DOCUMENTATION THROUGH |
| | FIELD UPLIFT TESTING IN ACCORDANCE WITH TAS 124. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED |
| | BY THE CODE, THE CONSTRUCTION DOCUMENTS SHALL |
| | ILLUSTRATE, DESCRIBE AND DELINEATE THE TYPE OF ROOFING |
| | SYSTEM, MATERIALS, FASTENING |
| | REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE |
| | RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT |
| | EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE |
| | WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE |
| | OR A STATEMENT BY AN ARCHITECT OR ENGINEER FOR THE |
| | SPECIFIC SITE MUST BE SUBMITTED WITH THE CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 4) UNDER THE ISSUED PERMIT SET OF PLANS THE WIND DESIGN |
| | CRITERIA IS FOUND ON SHEET S-2. |
| | 170 VULT |
| | 131.75 VASD |
| | EXPOSURE C |
| | WINDOW AND DOOR PRESSURES FOR REPLACED UNITS. |
| | THE MEAN ROOF HEIGHT NOT PROVIDED, NOR THE ROOF |
| | PRESSURES AT 10 SQ. FT. FOR ROOF ZONES 1, 2 OR 3. |
| | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | (3.) WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. |
| | (5.) DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| | M2). |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | NOTE IF THE DESIGN CRITERIA IS BY ANOTHER DESIGN |
| | PROFESSIONAL (ENGINEER OF RECORD) A DELEGATE ENGINEER |
| | THEN THE ROOF TOP DESIGN PRESSURES MUST BE REVIEWED BY |
| | THE ENGINEER OF RECORD. |
| | 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL |
| | 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD |
| | THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF |
| | RECORD FOR REVIEW. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |