| 2017-02-14 16:02:02 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17010633 |
| | ADD: 4395 EASLEY DR. / ADDITION OF A AERATION BLOWER |
| | NO. 10 |
| | CONT: TBD / TO BE DETERMINED |
| | TEL: 561-997-8070 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. FEB. 14/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) SHEET S01 PAD FOR MOUNTING TYP PUMP OR EQUIP. BASE |
| | SEEMS TO BE GENERIC, NO EQUIPMENT SPECS HAVE BEEN |
| | PROVIDED FOR THE NEW AERATION BLOWER # 10, NOR HAVE |
| | THEY BEEN REVIEWED BY THE DESIGNER OF RECORD TO SEE IF |
| | THE EQUIPMENT PAD IS SIZED CORRECTLY, THE OTHER UNKNOWN |
| | IS THE ANCHOR LOCATION TO ANCHOR THE NEW AERATION |
| | BLOWER. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2) THE STRUCTURAL SHEET DOES NOT HAVE ANY SEAL OR |
| | SIGNATURE. 61G15-23.005 PROCEDURES FOR SIGNING AND |
| | SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | |