| Plan Review Notes For Permit 17010618 |
| Permit Number |
17010618 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2017-09-28 18:29:06 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- ARCHITECT TO REVISE OVERHEAD GARAGE DOOR DESIGN | | | PRESSURES ON SHEET A3.2 TO CORRESPOND TO EXPOSURE "D". | | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: A) BALCONY | | | DECK UNDERLAYMENT. ARCHITECT TO SPECIFY BALCONY FLOOR | | | FINISH. NOTE: PRODUCT APPROVAL TO BE DESIGNED TO BE | | | USED W/ SPECIFIED FINISH. MARK ASSEMBLY TO BE USED AND | | | PROVIDE SIGNED/SEALED RAS 117 CALCULATIONS IF REQ'D. | | | B) OVERHEAD GARAGE DOOR THAT MEETS THE DESIGN | | | PRESSURES. COORDINATE WITH ITEM #1 ABOVE. | | | C) SINGLE HUNG WINDOWS FOR LARGE MISSILE IMPACT. | | | D) WINDOW MULLIONS AND SPECIFY MULLION SIZE. | | | E) FIXED WINDOWS AS SPECIFIED ON PLANS. | | | F) GUEST HOUSE EXTERIOR SWING DOOR AS SHOWN ON PLANS. | | | 3- ARCHITECT TO APPROVE ABOVE PRODUCT APPROVALS. | | | 4- ENGINEER'S RAS 117 CALCULATIONS SUBMITTED NEED | | | ORIGINAL SEAL & SIGNATURE (NOT COPY). CHAPTER 471 F.S. |
|