| | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | ELECTRICAL REVIEW COMMENTS. |
| | |
| | PLAN SHEET E2: |
| | |
| | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL BRANCH |
| | CIRCUITS SUPPLYING OUTLETS. FBC E3902.12, NEC 210.12 |
| | |
| | GFCI PROTECTED RECEPTACLES ARE REQUIRED AT THE REAR |
| | ELEVATION. NEC 210.8 |
| | |
| | CEILING ELECTRICAL BOXES SUPPORTING PADDLE FANS MUST BE |
| | LISTED FOR THAT USE. NEC 422.18; FBC R 3905.9 |
| | |
| | HIGH HAT CEILING LIGHTING FIXTURES IN INSULATED SPACES |
| | NEED TO BE RATED FOR INSULATION CONTACT (IC). NEC |
| | 410.116; FBC R 4004 |
| | |
| | A RECEPTACLE IS REQUIRED ON ANY WALL SPACE TWO FEET OR |
| | MORE IN WIDTH (KITCHEN). NEC 210.52(A)(2) |
| | |
| | ACCESS TO THE OUTSIDE AIR CONDITION UNIT DISCONNECTS |
| | MAY NOT BE BLOCKED BY THE UNITS. NEC 110.26 |
| | |
| | A DEDICATED LAUNDRY BRANCH CIRCUIT IS REQUIRED. NEC |
| | 210.52 (F), FBC R 3703.3 |
| | |
| | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO |
| | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND |
| | OUTSIDE EACH SLEEPING AREA. IF THE BUILDING HAS GAS |
| | APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE, A CARBON |
| | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH |
| | ROOM USED FOR SLEEPING. 2014 FBC R314, 315 |
| | |
| | A MINIMUM OF 75% OF THE LAMPS IN PERMANENTLY INSTALLED |
| | LIGHTING FIXTURES SHALL BE HIGH-EFFICACY LAMPS OR A |
| | MINIMUM OF 75% OF THE PERMANENTLY INSTALLED LIGHTING |
| | FIXTURES SHALL CONTAIN HIGH EFFICIENCY LAMPS. FBC |
| | ER404.1 |
| | |
| | PLAN SHEET E3: |
| | |
| | A RECEPTACLE IS REQUIRED ON ANY WALL SPACE TWO FEET OR |
| | MORE IN WIDTH (GUEST HOUSE). NEC 210.52(A)(2) |
| | |
| | A DEDICATED LAUNDRY BRANCH CIRCUIT IS REQUIRED. NEC |
| | 210.52 (F), FBC R 3703.3 |
| | |
| | |
| | AHU #3 REQUIRES AN EQUIPMENT DISCONNECT. NEC 422.30 FBC |
| | R E4101.5 |
| | |
| | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN |
| | SERVICE GROUND. NEC 250.94; FBC R E3609 |
| | |
| | PROVIDE A GROUND ROD AND GROUNDING ELECTRODE FOR GUEST |
| | HOUSE PANEL B. NEC 250.32 |
| | |
| | VERIFY THAT PANEL B HAS THE REQUIRED SAFETY CLEARANCES |
| | AND IS RATED FOR A WET LOCATION. NEC 110.26, 110.11 |
| | |
| | |