| 2018-05-17 07:49:18 | APPLICABLE CODES IN EFFECT: |
| | FLORIDA RES BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 |
| | |
| | PLAN REVIEW STATUS: DENIED. SEE COMMENTS BELOW: |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. PROVIDE AIC CALCULATIONS FOR NEW SERVICE SHOWN AND |
| | LABEL SERVICE EQUIPMENT AND PANEL BOARDS WITH AIC |
| | RATINGS. FBC 107.3.5 (AIC CALCULATION NOT PROVIDED. NEC |
| | 110.10) |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE |
| | PER FBC RES E3609.3 (NOT PROVIDED.) |
| | 5. CORRECTED. |
| | 6. CORRECTED. |
| | 7. CORRECTED. |
| | 8. CORRECTED. |
| | 9. ON MAIN SERVICE THE SERVICE CONDUCTORS CANNOT BE |
| | SHOWN WITH EQUIPMENT GROUNDING CONDUCTOR AS THE |
| | GROUNDED CONDUCTOR OR NEUTRAL WILL BE THE RETURN PATH |
| | BACK TO SOURCE. FBC RES E3607 (THE SERVICE CONDUCTORS |
| | TO THE FIRST MEANS OF DISCONNECT HAVE BEEN CORRECTED, |
| | HOWEVER, FROM THE FIRST MEANS OF DISCONNECT TO THE |
| | INTERIOR PANEL IS NOW SHOWN WITHOUT THE REQUIRED EGC. |
| | PROVIDE CORRECTION. NEC 250.122; FBC RE E3704.6, |
| | 3607.3.1) |
| | 10. GUEST HOUSE NOW ON SEPARATE PERMIT. |
| | 11. GUEST KITCHEN NOW ON SEPARATE PERMIT. |
| | 12. CORRECTED. |
| | 13. CORRECTED. |
| | 14. CORRECTED. |
| | 15. CORRECTED. |
| | 16. CORRECTED. |
| | 17. CORRECTED. |
| | |
| | NEW COMMENT: |
| | |
| | 18. PANEL A SHOWS A 6-3 ROMEX WIRE ON A 60 AMP BREAKER |
| | FOR AHU 1. THE ALLOWABLE AMPACITY FOR ROMEX WIRE SHALL |
| | NOT EXCEED THAT OF A 60 DEGREE CELCIUS RATING. |
| | THEREFORE, THE AMPACITY FOR 6-3 ROMEX IS 55 AMPS AND IS |
| | NOT SUFFICIENT FOR A 60 AMP CIRCUIT. PROVIDE |
| | CORRECTION. NEC 334.80; FBC RE E3705.4.4 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |