| Date |
Text |
| 2017-02-23 18:11:43 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION |
| | |
| | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS |
| | |
| | (1) PROVIDE REFRIGERANT PIPING DETAIL ON PLANS FOR THE |
| | GUEST HOUSE. |
| | (2) PROVIDE CONDENSER TIE DOWN DETAIL. |
| | |
| | FLORIDA ENERGY CODE FBC 2014 |
| | |
| | (3) PROVIDE ON THE PLANS WHO DREW THE PLANS. |
| | AS PER: |
| | R103.1 GENERAL. |
| | CONSTRUCTION DOCUMENTS AND OTHER SUPPORTING DATA SHALL |
| | BE SUBMITTED IN ONE OR MORE SETS WITH EACH APPLICATION |
| | FOR A PERMIT. THE CONSTRUCTION DOCUMENTS SHALL BE |
| | PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE |
| | REQUIRED BY THE STATUTES OF THE JURISDICTION IN WHICH |
| | THE PROJECT IS TO BE CONSTRUCTED. WHERE SPECIAL |
| | CONDITIONS EXIST, THE CODE OFFICIAL IS AUTHORIZED TO |
| | REQUIRE NECESSARY CONSTRUCTION DOCUMENTS TO BE PREPARED |
| | BY A REGISTERED DESIGN PROFESSIONAL. |
| | |
| | (4) PROVIDE HEAT LOAD CALCULATIONS WITH EQUIPMENT |
| | SIZING. |
| | AS PER: |
| | R403.6.1 EQUIPMENT SIZING. |
| | HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN |
| | ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT |
| | LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR |
| | OTHER APPROVED HEATING AND COOLING CALCULATION |
| | METHODOLOGIES, BASED ON BUILDING LOADS FOR THE |
| | DIRECTIONAL ORIENTATION OF THE BUILDING. THE |
| | MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR |
| | UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH |
| | THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN |
| | CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES |
| | NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR |
| | FUTURE EXPANSION OR OTHER FACTORS WHICH AFFECT |
| | EQUIPMENT SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT |
| | INCLUDE LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL |
| | VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM |
| | EXHAUST SYSTEMS. |
| | |
| | (5) PROVIDE AHRI OF ALL EQUIPMENT. |
| | |
| | JORGE VALIDO |
| | WPB MECHANICAL INSPECTOR/PLANS EXAMINER |
| | [email protected] |
| | 561-805-6716 |
| | |