Plan Review Notes
Plan Review Notes For Permit 17010600
Permit Number 17010600
Review Stop E
Sequence Number 1
Notes
Date Text
2017-02-13 09:43:42INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PROVIDE AIC CALCULATIONS FOR NEW SERVICE SHOWN AND
 LABEL SERVICE EQUIPMENT AND PANEL BOARDS WITH AIC
 RATINGS. FBC 107.3.5
 2. REVISE SERVICE CONDUCTORS, UNDERSIZED FOR A 200AMP
 SERVICE. 2/0 CONDUCTOR TO PROTECT 180AMP CALCULATED
 LOAD. FBC RES E3603
 3. GENERAL NOTE TO INDICATED REQUIRED SEPARATE PERMITS
 FOR LOW VOLTAGE SYSTEMS. FBC 107.3.5
 4. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE
 PER FBC RES E3609.3
 5. SHOW EXTERIOR RECEPTACLE AT FRONT ENTRANCE TO MAIN
 HOUSE PROTECTED BY GFCI DEVICE. FBC RES E3902.3
 6. PLEASE ADDRESS WALL SPACE RECEPTACLE REQUIREMENTS
 PER FBC RES E3901.2.2, 1. ANY SPACE THAT IS 2FT OR MORE
 IN WIDTH. SEE NEW GUEST ROOM AND ROOM ADJACENT TO
 KITCHEN.
 7. SMOKE DETECTORS TO MAINTAIN A 3FT CLEARANCE FROM FAN
 BLADES, FBC RES 314
 8. SHOW A RECEPTACLE W/P GFCI PROTECTED AT THE HVAC AC
 LOCATION FOR SERVICE PER FBC RES E3901.12 HVAC OUTLET/
 MAIN HOUSE
 9. ON MAIN SERVICE THE SERVICE CONDUCTORS CANNOT BE
 SHOWN WITH EQUIPMENT GROUNDING CONDUCTOR AS THE
 GROUNDED CONDUCTOR OR NEUTRAL WILL BE THE RETURN PATH
 BACK TO SOURCE. FBC RES E3607
 10. GUEST HOUSE: SHOW A RECEPTACLE W/P GFCI PROTECTED
 AT THE HVAC AC LOCATION FOR SERVICE PER FBC RES
 E3901.12 HVAC OUTLET/ MINI SPLITS
 11. GUEST KITCHEN RECEPTACLES TO LABELED GFCI
 PROTECTED. FBC RES E3902.6
 12. SHOW SMOKE DETECTORS FBC RES 314/315
 13. RECEPTACLE AT THE LAUNDRY ROOM 6FT OF SINK TO BE
 LABELED AS GFCI PROTECTED. FBC RES E3902.7
 14. PROVIDE A NOTE PER FBC ENERGY CONSERVATION CODE TO
 INDICATE; 75% OF LAMPS TO HIGH EFFICACY LAMPS.
 15. PLEASE SHOW ON PANELBOARD 20A CIRCUITS REQUIRED FOR
 DINING ROOM RECEPTACLES AND BATHROOM RECEPTACLES. FBC
 RES E3703.2 AND 4
 16. ELECTRICAL SHEET TO BE SIGNED AND SEALED BY
 DESIGNER OF RECORD OR ELECTRICAL QUALIFIER. FBC 107.3.5
 17. SHOW SMOKE DETECTORS ON DRAWINGS CLARIFY IF
 EXISTING OR NEW. FBC RES 314.
 18. COMMENTS MAT FOLLOW UPON RESUMITTAL. FEEL FREE TO
 CONTACT ME SHOULD YOU HAVE ANY QUESTIONS OR CONCERNS.
  
  