2017-02-22 17:46:49RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- THERE ARE TWO SEPARATE STRUCTURES. MAIN HOUSE AND
 GUEST HOUSE. NEED A PERMIT APPLICATION FOR EACH
 STRUCTURE. THIS WILL AVOID CONFUSION AND WILL
 FACILITATE PLAN REVIEW, INSPECTIONS AND RECORDS
 RETENTION. SEC. 105.1 AND SEC. 107.2.1.4 CITY
 AMENDMENTS.
  
 2-BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 3- PROPOSED GUEST HOUSE:
 A) NEW BEDROOM #2: IT APPEARS THAT 3043SH WINDOW
 DOESN'T COMPLY WITH EGRESS SEC. R310.1 FBC-RESIDENTIAL,
 5TH EDITION (2014). IT DOESN'T SEEM TO PROVIDE THE
 REQUIRED 24" CLEAR HEIGHT. PROVIDE MANUFACTURER'S CUT
 SHEETS SHOWING COMPLIANCE WITH THE EGRESS REQUIREMENTS.
  
 B) PROVIDE COMPLETE WALL SECTION FOR WALL LOCATED BY
 THE GARAGE DOORS. SPECIFY ALL FRAMING MEMBERS AND
 CONNECTORS. SPECIFY FINISHES ON BOTH SIDES. SEC. R301.1
 FBC-RESIDENTIAL.
  
 C) PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) GARAGE DOORS AS SHOWN ON PLANS.
  
 B) WINDOW MULLIONS AND CLEARLY SPECIFY MULLION SIZE TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES.
  
 C) ALL THE SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS/DETAILS AND SPECIFICATIONS. PROVIDE ONLY THE
 FLORIDA PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING
 THE SPECIFIED CONNECTOR OR DESIGNER OF RECORD TO LIST
 THE FLORIDA PRODUCT APPROVAL NUMBER NEXT TO EACH
 SPECIFIED CONNECTOR.
 NOTE: FLORIDA PRODUCT APPROVAL LISTED ON THE CONNECTOR
 SCHEDULE ON SHEET S-1.0 IS FOR THE 2010 CODE VERSION.
 NEED TO PROVIDE FLORIDA PRODUCT APPROVAL FOR THE 2014
 CODE VERSION.
  
 D) DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL THE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS.
  
 NOTE: COORDINATE WITH PRODUCT APPROVALS REQUIRED FOR
 THE MAIN HOUSE TO AVOID HAVING MORE THAN 2 COPIES FOR
 EACH PRODUCT APPROVAL.
  
 4- MAIN HOUSE: REMODELED BEDROOMS:
 A) IT APPEARS THAT 3043SH BEDROOM WINDOWS DON'T COMPLY
 WITH EGRESS SEC. R310.1 FBC-RESIDENTIAL. IT DOESN'T
 SEEM TO PROVIDE THE REQUIRED 24" CLEAR HEIGHT. PROVIDE
 MANUFACTURER'S CUT SHEETS SHOWING COMPLIANCE WITH THE
 EGRESS REQUIREMENTS.
  
 B) PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) WINDOW MULLIONS AS SHOWN ON PLANS AND CLEARLY
 SPECIFY MULLION SIZE TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES.
  
 B) ALL THE SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS/DETAILS AND SPECIFICATIONS. PROVIDE ONLY THE
 FLORIDA PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING
 THE SPECIFIED CONNECTOR OR DESIGNER OF RECORD TO LIST
 TH FLORIDA PRODUCT APPROVAL NUMBER NEXT TO EACH
 SPECIFIED CONNECTOR.
 NOTE: FLORIDA PRODUCT APPROVAL LISTED ON THE CONNECTOR
 SCHEDULE ON SHEET S-1.0 IS FOR THE 2010 CODE VERSION.
 NEED TO PROVIDE FLORIDA PRODUCT APPROVAL FOR THE 2014
 CODE VERSION.
  
 C) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 D) DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL THE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS.
  
 5- SECTION A/A-2 ON SHEET A-2.0:
 A) REVISE THE ROOF SLOPE TO COMPLY WITH SEC. R905.11.1
 FBC-RESIDENTIAL.
  
 B) ROOF SHEATHING SPECIFICATIONS DON'T MATCH ROOF
 SHEATHING SPECIFICATIONS SPECIFIED ON SHEET S-1.0.
 REVISE AS REQUIRED TO MATCH. CLARIFY ROOF SHEATHING
 THICKNESS AND NUMBER OF LAYERS. NOTE: SEC. R803.2.3.1
 FBC-RESIDENTIAL REQUIRES 8D RING SHANK NAILS MIN.
  
 C) ROOF INSULATION: THERE ARE TWO DIFFERENT TYPES OF
 INSULATION SPECIFIED. TAPERED INSULATION WITH THE ROOF
 ASSEMBLY AND R-30 BATT INSULATION BETWEEN ROOF JOISTS.
 CLARIFY IF BOTH INSULATIONS ARE GOING TO BE INSTALLED.
 COORDINATE WITH ROOFING PRODUCT APPROVAL SUBMITTED.
 SEC. R806 FBC-RESIDENTIAL.
  
 6- FOUNDATION PLAN ON SHEET S-1.0:
 A) IS MISSING THE CONCRETE BLOCK WALL VERTICAL
 REINFORCEMENT AS REQUIRED BY SEC. R609.3.3
 FBC-RESIDENTIAL. NOTE: SEE FOUNDATION NOTES ON SAME
 SHEET FOR REINFORCEMENT SPACING.
  
 B) PLAN SHOWS SEC. I/S-2. WHERE IS SECTION I/S-2?. SEC.
 107.2.1 CITY AMENDMENTS.
  
 7- ROOF FRAMING PLANS ON SHEET S-1.0:
 A) REVISE ROOF SLOPE TO COMPLY WITH SEC. R905.11.1
 FBC-RESIDENTIAL.
  
 B) PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE WITH
 THE CROSS VENTILATION AS REQUIRED BY SEC. R806
 FBC-RESIDENTIAL. SPECIFY HOW GETTING THE CROSS
 VENTILATION ON 2X12 SOLID ROOF JOISTS. NOTE: ALSO TAKE
 INTO ACCOUNT THAT THE 2X12 BLOCKING DOESN'T ALLOW AIR
 MOVEMENT.
  
 C) PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE WITH
 THE OVERFLOW DRAINS AND SCUPPERS AS REQUIRED BY SEC.
 R903.4.1 FBC-RESIDENTIAL.
  
 D) PLAN SHOWS SEC. I/S-2. WHERE IS SECTION I/S-2?. SEC.
 107.2.1 CITY AMENDMENTS.
  
 8- CURRENT CODE IS THE FBC 5TH EDITION (2014). NOTES ON
 DRAWINGS A-1.0, A-3.0 AND S-1.0 REFERENCE THE 2010 FBC.
 REVISE AS REQUIRED. CHAPTER 553 F.S.
  
 9- FLAT ROOF NOA'S SUBMITTED (NOA 15-0203.05 AND
 14-1030.02):
 A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE:
 COORDINATE WITH ITEM #5(C) ABOVE. IS IT GOING TO BE AN
 INSULATED FLAT ROOF ASSEMBLY OR ROOF IS GOING TO BE
 INSULATED BETWEEN ROOF JOISTS?
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF
 NOA'S. NOTE: CALCULATIONS ARE REQUIRED IF THE SELECTED
 ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF
 ZONES.
  
 10- PLANS NEED TO HAVE THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC.
 107.2.1 CITY AMENDMENTS. TILE BLOCK STATES THAT PLANS
 WERE DRAWN BY H.V.
 NOTE: IF THE DESIGNER IS THE CONTRACTOR, THEN
 CONTRACTOR TO PROVIDE PROOF THAT HE/SHE IS QUALIFIED TO
 CERTIFY PLANS AS REQUIRED BY SEC. 489.115 (4)(B)2. THE
 FOLLOWING IS A COPY OF THAT SECTION: ?"IN ADDITION, THE
 BOARD MAY APPROVE SPECIALIZED CONTINUING EDUCATION
 COURSES ON COMPLIANCE WITH THE WIND RESISTANCE
 PROVISIONS FOR ONE AND TWO FAMILY DWELLINGS CONTAINED
 IN THE FLORIDA BUILDING CODE AND ANY ALTERNATE
 METHODOLOGIES FOR PROVIDING SUCH WIND RESISTANCE WHICH
 HAVE BEEN APPROVED FOR USE BY THE FLORIDA BUILDING
 COMMISSION. DIVISION I CERTIFICATE-HOLDERS OR
 REGISTRANTS WHO DEMONSTRATE PROFICIENCY UPON COMPLETION
 OF SUCH SPECIALIZED COURSES MAY CERTIFY PLANS AND
 SPECIFICATIONS FOR ONE AND TWO FAMILY DWELLINGS TO BE
 IN COMPLIANCE WITH THE CODE OR ALTERNATE METHODOLOGIES,
 AS APPROPRIATE, EXCEPT FOR DWELLINGS LOCATED IN
 FLOODWAYS OR COASTAL HAZARD AREAS AS DEFINED IN SS.
 60.3D AND E OF THE NATIONAL FLOOD INSURANCE PROGRAM."
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED SHEET AND REMOVE OLD
 SHEET. DON'T STAPLE OLD SHEETS. SUBMITT OLD SHEETS FOR
 REFERENCE.
  