| Plan Review Notes For Permit 17010599 |
| Permit Number |
17010599 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-06-19 15:02:33 | 06/19/2018 2ND GAS REVIEW **DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | | | | 1. SECOND REQUEST ON SHEET. C-7 UNDER THE HEADING GAS | | | PIPING NOTES FOR LINE BETWEEN 2ND STAGE REGULATOR AND | | | GENERATOR NOTE #5 SHOULD READ 2014 FUEL GAS CODE NOT | | | 2010. PER WPB AMEND TO FBC 107.2.1 | | | | | | 2. SECOND REQUEST PLEASE PROVIDE SIZING TABLE THAT WERE | | | USED FOR THIS SYSTEM. PER WPB AMEND TO FBC 107.2.1. | | | | | | 3. SECOND REQUEST ON THE DISTANCE BETWEEN THE PROPANE | | | TANK AND GENERATOR SHOW 3?, THE TANK SHALL BE MIN OF | | | 10' FROM ANY SOURCE OF IGNITION ACCORDING TO NFPA TABLE | | | 6.3.4.3 SEPARATION DISTANCE BETWEEN CONTAINER PRESSURE | | | RELIEF VALVE AND BUILDING OPENINGS. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6720 | | | |
|