Plan Review Notes
Plan Review Notes For Permit 17010599
Permit Number 17010599
Review Stop G
Sequence Number 2
Notes
Date Text
2018-06-19 15:02:3306/19/2018 2ND GAS REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 1. SECOND REQUEST ON SHEET. C-7 UNDER THE HEADING GAS
 PIPING NOTES FOR LINE BETWEEN 2ND STAGE REGULATOR AND
 GENERATOR NOTE #5 SHOULD READ 2014 FUEL GAS CODE NOT
 2010. PER WPB AMEND TO FBC 107.2.1
  
 2. SECOND REQUEST PLEASE PROVIDE SIZING TABLE THAT WERE
 USED FOR THIS SYSTEM. PER WPB AMEND TO FBC 107.2.1.
  
 3. SECOND REQUEST ON THE DISTANCE BETWEEN THE PROPANE
 TANK AND GENERATOR SHOW 3?, THE TANK SHALL BE MIN OF
 10' FROM ANY SOURCE OF IGNITION ACCORDING TO NFPA TABLE
 6.3.4.3 SEPARATION DISTANCE BETWEEN CONTAINER PRESSURE
 RELIEF VALVE AND BUILDING OPENINGS.
  