| Plan Review Notes For Permit 17010599 |
| Permit Number |
17010599 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-09-29 13:29:41 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | GAS COMMENTS COMMENTS: | | | | | | 1. SHT. C-7 UNDER THE HEADING GAS PIPING NOTES FOR LINE | | | BETWEEN 2ND STAGE REGULATOR AND GENERATOR NOTE #5 | | | SHOULD READ 2014 FUEL GAS CODE NOT 2010. PER WPB AMEND | | | TO FBC 107.2.1 | | | | | | 2. PLEASE PROVIDE SIZING TABLE THAT WERE USED FOR THIS | | | SYSTEM. PER WPB AMEND TO FBC 107.2.1 | | | | | | 3. PLEASE SHOW DISTANCE BETWEEN THE PROPANE TANK AND | | | GENERATOR. THE TANK SHALL BE MIN OF 10' FROM ANY SOURCE | | | OF IGNITION .PER ASME 6.3.10. | | | | | | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND | | | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON | | | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|