2017-09-29 13:29:411ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 GAS COMMENTS COMMENTS:
  
 1. SHT. C-7 UNDER THE HEADING GAS PIPING NOTES FOR LINE
 BETWEEN 2ND STAGE REGULATOR AND GENERATOR NOTE #5
 SHOULD READ 2014 FUEL GAS CODE NOT 2010. PER WPB AMEND
 TO FBC 107.2.1
  
 2. PLEASE PROVIDE SIZING TABLE THAT WERE USED FOR THIS
 SYSTEM. PER WPB AMEND TO FBC 107.2.1
  
 3. PLEASE SHOW DISTANCE BETWEEN THE PROPANE TANK AND
 GENERATOR. THE TANK SHALL BE MIN OF 10' FROM ANY SOURCE
 OF IGNITION .PER ASME 6.3.10.
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  