Plan Review Notes
Plan Review Notes For Permit 17010577
Permit Number 17010577
Review Stop B
Sequence Number 1
Notes
Date Text
2017-01-30 16:35:08BUILDING PLAN REVIEW
 W. P. B. SUBMITTAL: 17010577
 W. P. B. PERMIT: 15050292
 ADD: 1100 S. FLAGLER DR.
 CONT: SUFFOLK
 TEL: ( 561) 282-3724/ TONY FIORITO
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JAN. 30/ 2017
 ACTION: DENIED
  
 SUBMITTAL- SUFFOLK HAS NOT SUBMITTED THE SUBMITTAL FORM
 NOR CONTACT INFORMATION.
  
 1) FORMWORK CALCULATIONS FOR SHORING UNDER LEVEL P1 THE
 COVERSHEET DOES COMPLY WITH THE REQUIREMENT FOR DIGITAL
 SIGNATURES PARTLY. THE COVERSHEET DOES NOT LIST HOW
 MANY PAGES ARE COVERED UNDER THIS SEAL. PAGE 2 OF THE
 REPORT DOES HAVE A TABLE OF CONTENT BUT NOT SEALED.
  
 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX
 SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND
 THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE
 PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE
 COVERED UNDER THE COVER SHEET OR INDEX SHEET.
  
 2) CORRECTED, ADJUSTED COMMENT. WAS TOLD PROBLEMS WITH
 LOADING OF THE 4 SHEETS, NO ACTION IS REQUIRED.
 SHEETS F0, F1, F2 & FA ARE NOT SIGNED WITH AN
 ELECTRONIC SIGNATURE.
  
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 3) MISSING THE CONTRACTOR LETTER OF COMPLIANCE. 2010
 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES, PLANS
 AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  