2017-05-16 11:44:432ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17010555
 5/16/17
  
 RESULTS: DENIED.
  
 1) THE REVISED SHEET M-2.4B WHICH IS PART OF THIS
 REVISION PER THE ARCHITECT'S NARRATIVE, WAS NOT
 UPLOADED FOR REVIEW- PLEASE PROVIDE THE SHEET.
  
 2) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 POOL BATHROOMS AC SYSTEM, AND REVISE THE ENERGY
 CALCULATIONS AND AC EQUIPOMENT SCHEDULE TO INCLUDE THE
 SYSTEM.
  
 3) M-4.1, UNIT A1: IT APPEARS THAT EF-1 IS UTILIZING
 TWO EXHAUST DUCTS AND TWO EXHAUST TERMINATIONS- PLEASE
 CLARIFY.
  
 4) COMMENT #2 FROM THE 1ST REVIEW STILL EXISTS.
 MANUFACTURER'S SPECIFICATIONS FOR THE FIRST COMPANY
 UNIT INDICATE "HOT DISCHARGE AIR" COMING OUT OF THE
 CONDENSER. PLEASE RELOCATE ALL O/A INTAKES WITHIN 10'
 HORIZONTALLY OF THE CONDENSER- SECTION 401.4
  
 5) PROVIDE AHRI CERTIFICATES FOR THE FIRST COMPANY
 SYSTEMS TO VERIFY THEY ARE RATED AT 14 SEER.
  
 6) NOW THAT THE EMS IS ELIMINATED PLEASE INDICATE
 COMPLIANCE WITH HVAC SYSTEM CONTROLS AS REQUIRED BY
 SECTION C403.2.4- C403.2.4.4 FBC-14 ENERGY
 CONSERVATION.
  