| 2017-02-24 07:13:57 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #1701055 | | | 2/24/17 | | | | | | 1) PLEASE PROVIDE A NARRATIVE FORM THE DESIGN | | | PROFESSIONAL THAT ITEMIZES SHEET-BY-SHEET WHAT CHANGES | | | WERE MADE TO THE APPROVED PLANS. PLEASE NOTE THAT THE | | | NEW UPLOADED SHEETS M-5.1 & M-5.2 DO NOT APPEAR TO HAVE | | | BEEN REVISED. | | | | | | 2) THE REVISED LOCATIONS OF THE O/A INLETS FOR THE | | | APARTMENT AC SYSTEMS AND SOME OF THE EXISTING LOCATIONS | | | APPEAR TO BE WITHIN 10' OF THE EXHAUST FROM THE | | | CONDENSER- SEE SECTION 401.4. | | | | | | 3) REFER TO SECTION 401.5 AND INDICATE WHAT TYPE OF | | | CORROSION RESISTANT PROTECTION WILL BE INSTALLED OVER | | | THE O/A INTAKES OPENINGS- SCREENS, LOUVERS, OR GRILLS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|